3-42
Programming and Parameters
Advance Program Group
(continued)
A182 [Drive OL Mode]
Related Parameter(s):
,
Determines how the drive handles overload conditions that would otherwise cause the drive to fault.
Options
0
“DIsabled”
1
“Reduce CLim”
2
“Reduce PWM”
3
“Both-PWM 1st” (Default)
A183 [SW Current Trip]
Related Parameter(s):
Enables/disables a software instantaneous (within 100 ms) current trip.
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/(Drive Rated Amps
×
1.8)
Display:
0.1 Amps
A184 [Load Loss Level]
Related Parameter(s):
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified
in [Load Loss Time].
Values
Default:
0.0 (Disabled)
Min/Max:
0.0/Drive Rated Amps
Display:
0.1 Amps
A185 [Load Loss Time]
Related Parameter(s):
Sets the required time for the current to be below [Load Loss Level] before a Load Loss fault occurs.
Values
Default:
0 Secs (Disabled)
Min/Max:
0/9999 Secs
Display:
1 Secs
A186 [Stall Fault Time]
Sets the time that the drive will remain in stall mode before a fault is issued.
Options
0
“60 Seconds” (Default)
1
“120 Seconds”
2
“240 Seconds”
3
“360 Seconds”
4
“480 Seconds”
5
“Flt Disabled”
Содержание PowerFlex400
Страница 1: ...Adjustable Frequency AC Drive for Fan Pump Applications FRN 4 xx User Manual www abpowerflex com...
Страница 42: ...1 32 Installation Wiring Notes...
Страница 52: ...2 10 Start Up Notes...
Страница 112: ...3 60 Programming and Parameters Notes...
Страница 128: ...A 8 Supplemental Drive Information Notes...
Страница 164: ...D 14 Application Notes Notes...
Страница 170: ...E 6 Modbus RTU Protocol Notes...
Страница 178: ...F 8 Metasys N2 Notes...
Страница 190: ...Index 4...
Страница 191: ......