Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
65
Frame A Field Controller Part Replacement Procedures
Chapter 3
10. For devices with AC current transducers with no connection bars, turn
the board over and remove the two screws and washers that secure the
AC current transducers to the board. Remove the AC current
transducers and windings (if present) from the device.
Install the Power Traces Circuit Board
Install the power traces circuit board in reverse order of removal.
• Verify that the connecting wire on the board is placed in the exact
location as previously installed.
• Verify that the wire leads wound around the current transducers (if
present) are in the same location as when previously installed.
IMPORTANT
You do not need to remove the windings from the AC current
transducers.