Component Test Procedures
Chapter 2
Figure 6 - Frame B SCR Module Gate-Lead Connection Pinouts
Check the Pulse Transformer Board
The pulse transformer circuit board contains an isolated gate firing circuit and
also provides dv/dt protection for the SCR modules. One of these conditions
can indicate a malfunction of these devices:
• An Overcurrent fault (F13
• A blown or tripped incoming protection device
• Erratic motor operation
Use the following procedure if a malfunction in this circuitry is suspected.
1. Read the General Safety Precautions on page
2. Remove power from the device.
• For frame A devices, see page
• For frame B devices, see page
3. Remove the protective covers from the device.
• For frame A devices, see page
• For frame B devices, see page
4. Remove the control electromagnetic interference (EMI) shield and
control board.
• For frame A devices, see Control EMI Shield and Control Circuit
Board Replacement page
.
• For frame B devices, see Remove the Communication Adapter and
Electromagnetic Interference Shield page
1
2
3
2
1
3
1
2
3
2
1
3
1
2
3
2
1
3
1
01
2
02
3
03
5 4
7 6
5 4
7 6
5 4
7 6
4 5
6 7
4 5
6 7
4 5
6 7
Gate Lead
Pinouts
Gate Lead
Pinouts
SCR
Содержание 23PFC
Страница 8: ...8 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Preface Notes ...
Страница 130: ...130 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix A Schematics Notes ...
Страница 142: ...142 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix B Circuit Board Layouts and Connections Notes ...
Страница 148: ...148 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Index Notes ...
Страница 149: ......