14
Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
Chapter 2
Component Test Procedures
Save the Parameter
Configuration
It is recommended that you save the field controller and communication
adapter parameter configuration before performing any service. You can save
the device configuration by using one of these methods:
• HIM Set - see Save to a HIM Set.
• Download the field controller and adapter parameters to an offline
database file by using DriveExecutive™. See the on-line help that is
provided with DriveExecutive for information on how to save
database files.
• Export a configuration file by using Connected Components
Workbench® software. See the on-line help that is provided with
Connected Components Workbench for information on how to
export a device configuration file.
Save to a HIM Set
Follow these steps to save the device and adapter parameters to a HIM set.
1. On the HIM, access the Memory Storage menu.
2. Select the HIM CopyCat menu and press
.
3. Select Device -> HIM and press
.
4. Do one of the following:
• If there is no existing HIM Set, enter a name using the
and
buttons to select the desired characters and press
.
• If there is an existing HIM Set, press
to overwrite it, or select
No using the
button and use the
and
buttons to
select the desired characters. Then press
.
The HIM Set will be saved to nonvolatile memory.
Содержание 23PFC
Страница 8: ...8 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Preface Notes ...
Страница 130: ...130 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix A Schematics Notes ...
Страница 142: ...142 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Appendix B Circuit Board Layouts and Connections Notes ...
Страница 148: ...148 Rockwell Automation Publication 23PFC TG001A EN P March 2018 Index Notes ...
Страница 149: ......