Chapter 5
Start-up after Repair
8.
Verify that the following parameter values are set correctly:
•
175 [Load Rated Volt] is set to the load nominal (rated) voltage for the
field controller.
•
179 [Load Rated Curr] is set to the load nominal (rated) current.
•
481 [UnderVolt Thresh] is set to an appropriate value - typically 85% of
the nominal AC line voltage.
9.
Complete the Verify Field Controller Operation section of Chapter 1
Startup in the PowerFlex® DC Field Controller Programming Manual,
publication