Rockwell Automation Publication 23PFC-TG001A-EN-P - March 2018
79
Frame B Field Controller Part Replacement Procedures
Chapter 4
Remove Power from the
Device
Remove and lock-out all incoming power to the device.
DPI / HIM Assembly
Replacement
Remove the DPI / HIM Assembly
1. Read the General Safety Precautions on page
2. Remove power from the device (see page
3. Disconnect the DPI cable from the HIM assembly.
ATTENTION:
Remove power before you make or break cable connections.
When you remove or insert a cable connector with power applied, an
electrical arc can occur. An electrical arc can cause personal injury or property
damage by:
• sending an erroneous signal to your system field devices, causing unintended
machine motion
• causing an explosion in a hazardous environment
Electrical arcing causes excessive wear to contacts on both the module and its
mating connector. Worn contacts can create electrical resistance.