Programming and Parameters
Chapter 3
T086 [Analog Out2 High]
Scales the Maximum Output Value for the A065 [Analog Out Sel] source setting.
Examples:
.
Values
Default:
100%
Min/Max:
0/800%
Display:
1%
T086 Setting
T085 Setting
T085 Max. Output Value
50%
1 “OutCurr 0-10”
5V for 200% Drive Rated Output Current
90%
11 “OutPowr 0-20”
18mA for 200% Drive Rated Power
T087 [Anlg Out2 Setpt]
Sets direct parameter control over the analog output. If enabled, this sets the percent value of analog output.
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
T088 [Anlg Loss Delay]
,
Sets the length of time after power-up during which the drive will not detect an analog signal loss. The drive response to an analog signal loss is set in
[Analog In x
Loss].
Values
Default:
0.0 Secs
Min/Max:
0.0/20.0 Secs
Display:
0.1 Secs
T089 [Analog In Filter]
Sets level of additional filtering of the analog input signals. A higher number increases filtering and decreases bandwidth. Each setting doubles the applied filtering (1 = 2x filter, 2
= 4x filter, etc.). No additional filtering is applied when set to “0”.
Values
Default:
0
Min/Max:
0/14
Display:
1
T090 [Sleep Sel]
,
,
,
(with FRN 7.xx and later.)
Selects the operation of the sleep function.
Options
0 “AI1 > SlpLvl” (Default)
Sleep enabled from Analog Input 1 (d305 [Analog In 1]) above sleep level.
1 “AI1 < SlpLvl”
Sleep enabled from Analog Input 1 (d305 [Analog In 1]) below sleep level.
2 “AI2 > SlpLvl”
Sleep enabled from Analog Input 2 (d306 [Analog In 2]) above sleep level.
3 “AI2 < SlpLvl”
Sleep enabled from Analog Input 2 (d306 [Analog In 2]) below sleep level.
4 “OFrq>SlpLvl”
Sleep enabled based on drive output frequency (b001 [Output Freq]) above sleep level.
5 “OFrq>SlpLvl”
Sleep enabled based on drive output frequency (b001 [Output Freq]) below sleep level.
6 “CFrq>SlpLvl”
Sleep enabled based on drive command frequency (b002 [Commanded Freq]) above sleep level.
7 “CFrq>SlpLvl”
Sleep enabled based on drive command frequency (b002 [Commanded Freq]) below sleep level.
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......