122
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Appendix A
Supplemental Drive Information
Specifications
Drive Ratings
Catalog Number
Output Ratings
Input Ratings
Branch Circuit Protection
kW (HP)
Amps
Voltage
Range
kVA
Amps Fuses 140M Motor
Protectors
(1)(2)
Contactors Min.
Enclosure
Volumes
(3)
(in.
3
)
45 °C 50 °C
200...240V AC – 3-Phase Input, 0 - 230V 3-Phase Output
22C-B012N103
2.2 (3.0)
12
12
180-265
6.5
15.5
20
140M-F8E-C16
100-C23
5098
22C-B017N103
3.7 (5.0)
17.5
17.5
180-265
8.8
21
30
140M-F8E-C25
100-C37
5098
22C-B024N103
5.5 (7.5)
24
24
180-265
10.9
26.1
35
140M-F8E-C32
100-C37
5098
22C-B033N103
7.5 (10)
33
33
180-265
14.4
34.6
45
140M-F8E-C45
100-C45
5098
22C-B049A103
11 (15)
49
49
180-265
21.3
51
70
–
100-C60
–
22C-B065A103
15 (20)
65
65
180-265
28.3
68
90
–
100-C85
–
22C-B075A103
18.5 (25)
75
75
180-265
32.5
78
100
–
100-D95
–
22C-B090A103
22 (30)
90
81
180-265
38.3
92
125
–
100-D110
–
22C-B120A103
30 (40)
120
120
180-265
51.6
124
175
–
100-D180
–
22C-B145A103
37 (50)
145
130
180-265
62.4
150
200
–
100-D180
–
380...480V AC – 3-Phase Input, 0...460V 3-Phase Output
22C-D6P0N103
2.2 (3.0)
6
6
340-528
6.3
7.5
10
140M-D8E-C10
100-C09
5098
22C-D010N103
4.0 (5.0)
10.5
10.5
340-528
10.9
13
20
140M-D8E-C16
100-C16
5098
22C-D012N103
5.5 (7.5)
12
12
340-528
11.9
14.2
20
140M-D8E-C16
100-C23
5098
22C-D017N103
7.5 (10)
17
17
340-528
15.3
18.4
25
140M-D8E-C20
100-C23
5098
22C-D022N103
11 (15)
22
22
340-528
19.2
23
30
140M-F8E-C32
100-C30
5098
22C-D030N103
15 (20)
30
27
340-528
25.8
31
40
140M-F8E-C32
100-C37
5098
22C-D038A103
18.5 (25)
38
38
340-528
33.3
40
50
140M-F8E-C45
100-C60
9086
22C-D045A103
22 (30)
45.5
45.5
340-528
39.1
47
60
–
100-C60
–
22C-D060A103
30 (40)
60
54
340-528
53.3
64
80
–
100-C85
–
22C-D072A103
37 (50)
72
72
340-528
60.7
73
100
–
100-C85
–
22C-D088A103
45 (60)
88
88
340-528
74.9
90
125
–
100-D110
–
22C-D105A103
55 (75)
105
105
340-528
89
107
150
–
100-D140
–
22C-D142A103
75 (100)
142
128
340-528
124.8 150
200
–
100-D180
–
22C-D170A103
90 (125)
170
170
340-528
142
170
250
–
100-D250
–
22C-D208A103
110 (150)
208
208
340-528
167
200
250
–
100-D250
–
22C-D260A103
132 (200)
260
260
340-528
196
235
300
–
100-D300
–
22C-D310A103
160 (250)
310
290
340-528
242
290
400
–
100-D420
–
22C-D370A103
200 (300)
370
370
340-528
304
365
500
–
100-D420
–
22C-D460A103
250 (350)
460
410
340-528
387
465
600
–
100-D630
–
(1) The AIC ratings of the Bulletin 140M Motor Protector Circuit Breakers may vary. See
Bulletin 140M Motor Protection Circuit Breakers
(2) Manual Self-Protected (Type E) Combination Motor Controller, UL listed for 208 Wye or Delta, 240 Wye or Delta, 480Y/277 or 600Y/347. Not UL
listed for use on 480V or 600V Delta/Delta, corner ground, or high-resistance ground systems.
(3) When using a Manual Self-Protected (Type E) Combination Motor Controller, the drive must be installed in a ventilated or non-ventilated
enclosure with the minimum volume specified in this column. Application specific thermal considerations may require a larger enclosure.
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......