30
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1
Installation/Wiring
(6) Common for Analog Input 2 (AI2). Electronically isolated from digital I/O and opto output. Not to be used with Analog Input 1
(AI1), Analog Output 1 (AO1) or Analog Output 2 (AO2). With Analog Input 2, provides one fully isolated analog input channel.
Table 9 - Control I/O Terminal Designations
No.
Signal
Default
Description
Param.
01
Stop
(1)
/
Function Loss
Coast
Factory installed jumper or a normally closed input
must be present for the drive to start.
Program with P036 [Start Source].
(1)
02
Start/Run FWD
–
HAND Mode: Command comes from Integral Keypad.
AUTO Mode: I/O Terminal 02 is active.
Program with P036 [Start Source].
,
03
Direction/Run REV
Rev Disabled
To enable reverse operation, program with A166
[Reverse Disable].
Program with P036 [Start Source].
,
,
04
Digital Common
–
For digital inputs. Tied to I/O Terminal 09.
Electronically isolated with digital inputs from analog
I/O and opto output.
05
Digital Input 1
Purge
(2)
Program with T051 [Digital In1 Sel].
06
Digital Input 2
Local
Program with T052 [Digital In2 Sel].
07
Digital Input 3
Clear Fault
Program with T053 [Digital In3 Sel].
08
Digital Input 4
Comm Port
Program with T054 [Digital In4 Sel].
09
Digital Common
–
For digital inputs. Tied to I/O Terminal 04.
Electronically isolated with digital inputs from analog
I/O and opto output.
10
Opto Common
–
For opto-coupled outputs. Electronically isolated with
opto output from analog I/O and digital inputs.
11
+24V DC
–
Drive supplied power for digital inputs.
Referenced to Digital Common. Max. Output: 100mA.
12
+10V DC
–
Drive supplied power for 0-10V external
potentiometer.
Referenced to Analog Common. Max. Output: 15mA.
13
Analog Input 1
0-10V
External 0-10V (unipolar), 0-20mA or 4-20mA input
supply or potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI1 DIP Switch to 20mA.
Program with T069 [Analog In 1 Sel].
Input Impedance:
100k ohm (Voltage Mode)
250 ohm (Current Mode)
14
Analog Common 1
–
Common for Analog Input 1 and Analog Output 1 and
2. Electrically isolated from digital I/O and opto
output.
15
Analog Output 1
OutFreq 0-10
Default analog output is 0-10V.
For current (mA) value, set AO1 DIP Switch to 20mA.
Program with T082 [Analog Out1 Sel].
Maximum Load:
4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
,
...
16
Analog Output 2
OutCurr 0-10
Default analog output is 0-10V.
For a current (mA) value, set AO2 DIP Switch to 20mA.
Program with T085 [Analog Out2 Sel].
Maximum Load:
4-20mA = 525 ohm (10.5V)
0-10V = 1k ohm (10mA)
17
Analog Input 2
0-10V
Optically isolated external 0-10V (unipolar), ±10V
(bipolar), 0-20mA or 4-20mA input supply or
potentiometer wiper. Default input is 0-10V.
For current (mA) input, set AI2 DIP Switch to 20mA.
Program with T073 [Analog In 2 Sel].
Input Impedance:
100k ohm (Voltage Mode)
250 ohm (Current Mode)
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......