Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
67
Programming and Parameters
Chapter 3
T055 [Relay Out1 Sel]
,
,
,
Sets the condition that changes the state of the output relay contacts.
Options
0 “Ready/Fault” (Default)
Relay changes state when power is applied. This indicates that the drive is ready for operation. Relay returns drive to shelf state
when power is removed or a fault occurs.
1 “At Frequency”
Drive reaches commanded frequency
2 “MotorRunning”
Motor is receiving power from the drive.
3 “Hand Active”
Active when drive is in local control.
4 “Motor Overld”
Motor overload condition exists.
5 “Ramp Reg”
Ramp regulator is modifying the programmed accel/decel times to avoid an overcurrent or overvoltage fault from occurring.
6 “Above Freq”
• Drive exceeds the frequency (Hz) value set in
[Relay Out1 Level].
• Use T056 to set threshold.
7 “Above Cur”
• Drive exceeds the current (% Amps) value set in
[Relay Out1 Level].
• Use T056 to set threshold.
8 “Above DCVolt”
• Drive exceeds the DC bus voltage value set in
[Relay Out1 Level].
• • Use T056 to set threshold.
9 “Above Anlg 2”
• Analog input voltage (I/O Terminal 17) exceeds the value set in
[Analog In 2 Sel] is set to 3 “Voltage Mode - Bipolar”.
• This parameter setting can also be used to indicate a PTC trip point when the input (I/O Terminal 17) is wired to a PTC and
external resistor.
• Use T056 to set threshold.
10 “Above PF Ang”
• Power Factor angle has exceeded the value set in
[Relay Out1 Level].
• Use T056 to set threshold.
11 “Anlg In Loss”
Analog input loss has occurred. Program
[Analog In 1 Loss] and/or
[Analog In 2 Loss] for desired action when input
loss occurs.
12 “ParamControl”
Enables the output to be controlled over network communications by writing to
[Relay Out1 Level]. (0 = Off, 1 = On.)
13 “Retries Exst”
Value set in
[Auto Rstrt Tries] is exceeded.
14 “NonRec Fault”
• Number of retries for
[Auto Rstrt Tries] is exceeded, or
• Non-resettable fault occurs, or
•
[Auto Rstrt Tries] is not enabled.
15 “Reverse”
Drive is commanded to run in reverse direction.
16 “Logic In 1”
An input is programmed as “Logic In 1” and is active.
17 “Logic In 2”
An input is programmed as “Logic In 2” and is active.
23 “Aux Motor”
Auxiliary Motor is commanded to run. Refer to
for details.
24 “Fault” (with FRN 7.xx and later) Relay remains in the off state when power is applied to the drive and energizes when a fault occurs. This is inverted from Option
0, “Ready/Fault”.
IMPORTANT
Value for
[Relay Out1 Level] must be entered in percent of drive rated output current.
T056 [Relay Out1 Level]
32 bit parameter.
Sets the trip point for the digital output relay if the value of
[Relay Out1 Sel] is 6, 7, 8, 9, 10 or 12.
Values
Default:
0.0
Min/Max:
0.0/9999
Display:
0.1
32
T055 Setting
T056 Min/Max
6
0/320 Hz
7
0/180%
8
0/815 Volts
9
0/100%
10
1/180 degs
12
0/1
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......