Basic Display Group
b001 [Output Freq]
Related Parameter(s):
,
Output frequency present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.00/
[Maximum Freq]
Display:
0.01 Hz
b002 [Commanded Freq]
Related Parameter(s):
,
Value of the active frequency command. Displays the commanded frequency even if the drive is not running.
Values
Default:
Read Only
Min/Max:
0.00/
[Maximum Freq]
Display:
0.01 Hz
IMPORTANT
The frequency command can come from a number of sources. See
Start and Speed Reference Control on page 37
for more information.
b003 [Output Current]
The output current present at T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0.0/(Drive Rated Amps × 2)
Display:
0.1 Amps
b004 [Output Voltage]
,
Output voltage present at terminals T1, T2 & T3 (U, V & W).
Values
Default:
Read Only
Min/Max:
0/510
Display:
1 VAC
b005 [DC BusVoltage]
Present DC bus voltage level.
Values
Default:
Read Only
Min/Max:
0/820
Display:
1 VDC
b006 [Drive Status]
Present operating condition of the drive.
Values
Default:
Read Only
Min/Max:
0/1
Display:
1
1 = Condition True, 0 = Condition False
Running
Bit 1
Forward
Bit 2
Accelerating
Bit 3
Decelerating
Bit 4
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......