26
Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1
Installation/Wiring
Figure 9 - Power Terminal Blocks (Frames E through H)
IMPORTANT
For Frame E, 240V 30...37 kW (40...50 HP) and 480V 55...75 kW (75...100 HP)
drives, take care to place the wire beneath the jumper and not above it when
connecting to terminals P1 and P2.
R/L1 S/L2 T/L
3
P1
P2
DC– U/T1 V/T2 W/T
3
Frame E:
240V
480V
30-37 kW 55-75 kW
(40-50 HP) (75-100 HP)
Frame F
R/L1 S/L2 T/L
3
P1
P2 DC–
U/T1 V/T2 W/T
3
Frame G
R/L1 S/L2 T/L
3
P1
P2
DC– U/T1 V/T2 W/T
3
Frame H
R/L1
S/L2
T/L
3
DC–
DC+
U/T1
V/T2
W/T
3
Frame E:
480V
37-45 kW
(50-60 HP)
R/L1S/L2T/L
3
P1 P2 DC–
U/T1V/T2W/T
3
See note at the bottom
of this page.
P1
P2
DC-
P1
P2
DC-
Bottom view of terminal block and wire
Jumper
Wire
Wire
Jumper
Correct
Incorrect
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......