Rockwell Automation Publication 22C-UM001J-EN-E - January 2017
Chapter 1
Installation/Wiring
Storage
• Store within an ambient temperature range of -40° to +85°C.
• Store within a relative humidity range of 0% to 95%,non-condensing.
• Do not expose to a corrosive atmosphere.
AC Supply Source
Considerations
Ungrounded Distribution Systems
Disconnecting MOVs (Drive Frames C, E and F only.)
To prevent drive damage, the MOVs connected to ground shall be
disconnected if the drive is installed on an ungrounded distribution system
where the line-to-ground voltages on any phase could exceed 125% of the
nominal line-to-line voltage. To disconnect these devices, remove the jumper
shown in
Figure 5 - Phase to Ground MOV Removal
Figure 6 - MOV Jumper Location
ATTENTION:
PowerFlex 400 drive frames contain protective MOVs that are
referenced to ground. These devices must be disconnected if the drive is
installed on an ungrounded or resistive grounded distribution system.
R/L1
S/L2
T/L
3
1
2
3
4
Three-Phase
AC Input
Jumper
Frame C
Frame E and F (Typical)
Important:
Tighten screw after jumper removal.
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......