Programming and Parameters
Chapter 3
Basic Program Group
P031 [Motor NP Volts]
,
Stop drive before changing this parameter.
Set to the motor nameplate rated volts.
Values
Default:
Based on Drive Rating
Min/Max:
20/Drive Rated Volts
Display:
1 VAC
P032 [Motor NP Hertz]
,
Stop drive before changing this parameter.
Set to the motor nameplate rated frequency.
Values
Default:
60 Hz
Min/Max:
15/320 Hz
Display:
1 Hz
P033 [Motor OL Current]
,
Set to the maximum allowable motor current. The drive will fault on an F7
if the value of this parameter is exceeded by 150% for 60 seconds.
Values
Default:
Drive Rated Amps
Min/Max:
0.0/(Drive Rated Amps × 2)
Display:
0.1 Amps
P034 [Minimum Freq]
Related Parameter(s):
,
,
Set to the maximum allowable motor current. The drive will fault on an F7
if the value of this parameter is exceeded by 150% for 60 seconds.
Values
Default:
Drive Rated Amps
Min/Max:
0.0/(Drive Rated Amps × 2)
Display:
0.1 Amps
P035 [Maximum Freq]
Related Parameter(s):
,
,
,
,
Stop drive before changing this parameter.
Sets the highest frequency the drive will output.
Values
Default:
60.0 Hz
Min/Max:
0.0/320.0 Hz
Display:
0.1 Hz
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......