Chapter 3
Programming and Parameters
T072 [Analog In 1 Loss]
Related Parameter(s):
,
,
,
,
Stop drive before changing this parameter.
Selects drive action when an input signal loss is detected. Signal loss is defined as an analog signal less than 1V or 2mA. The signal loss event ends and normal operation resumes
when the input signal level is greater than or equal to 1.5V or 3mA. If using a 0-10V analog input, set
[Analog In 1 Lo] to a minimum of 20% (i.e. 2 volts).
The drive will fault on an F29
when the analog signal is lost if this parameter is used for the PID feedback, and this parameter and
[PID Ref Sel] are both set
to an option other than 0 “Disabled”.
Options
0 “Disabled” (Default)
1 “Fault (F29)”
F29 Analog Input Loss
2 “Stop”
Uses P037 [Stop Mode]
3 “Zero Ref”
Drive runs at zero speed reference.
4 “Min Freq Ref”
Drive runs at minimum frequency.
5 “Max Freq Ref”
Drive runs at maximum frequency.
6 “Preset Freq0”
Drive runs at A143 [Preset Freq 0].
7 “Hold Last” (with FRN 6.xx and
later)
Drive uses last frequency command from analog input prior to signal loss, or last PID reference prior to signal loss when used as a
PID reference.
T073 [Analog In 2 Sel]
,
,
,
,
Sets the analog input signal mode (0-20mA, 4-20mA, 0-10V, -10 to +10V). This parameter must match DIP Switch AI2 setting on the control board.
.
Values
Default:
2
Min/Max:
0/7
Display:
1
T073 Option
Setting
Input Range
DIP Switch AI1 Setting
0
Current Mode
0-20 mA
20 mA
1
Current Mode
4-20 mA
20 mA
2
Voltage Mode - Unipolar
0-10V
10V
3
(1)
(1) Setting 3 is only available on [Analog In 2 Sel]. Input 2 is isolated and supports a bi-polar input, so that setting 3
determines if the voltage input is enabled for bipolar control. If bipolar is selected, P034 [Minimum Freq] and
T074 [Analog In 2 Lo] are ignored. If input 2 is set up for current control, Bipolar mode is not possible. If the
analog input is inverted ([Analog In 2 Lo] > [Analog In 2 Hi]), Bipolar mode is disabled and this input uses
unipolar control only (negative values are treated like zero).
Voltage Mode - Bipolar
-10 to +10V
10V
4
Current Mode (Square Root)
0-20 mA
20 mA
5
Current Mode (Square Root)
4-20 mA
20 mA
6
Voltage Mode - Unipolar (Square Root) 0-10V
10V
7
Voltage Mode - Bipolar (Square Root)
-10 to +10V
10V
T074 [Analog In 2 Lo]
,
,
,
,
Stop drive before changing this parameter.
Sets the analog input level that corresponds to
[Minimum Freq].
Analog inversion can be accomplished by setting this value larger than
[Analog In 2 Hi].
Values
Default:
0.0%
Min/Max:
0.0/100.0%
Display:
0.1%
IMPORTANT
If analog inversion is implemented the drive will go to maximum frequency in the event the analog input is lost. It is strongly recommended to activate
[Analog In 1 Loss] to protect from this potential occurrence.
0
P035 [Maximum Freq]
P034 [Minimum Freq]
T074 [Analog In 2 Lo]
T075 [Analog In 2 Hi]
0
Speed Reference
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......