Chapter 4
Troubleshooting
F12
HW OverCurrent
2
The drive output current has
exceeded the hardware current limit.
Check programming. Check for
excess load, improper
Select] setting, DC brake volts set
too high or other causes of excess
current.
F13
Ground Fault
2
A current path to earth ground has
been detected at one or more of the
drive output terminals.
Check the motor and external wiring
to the drive output terminals for a
grounded condition.
F15
Load Loss
1
Output current has dropped below
the level set in
[Load Loss
Level].
Check for load loss (i.e., a broken
belt).
F17
Input Phase Loss
(FRN 6.xx and
later)
2
Excessive DC bus ripple voltage
detected. See
[DC Bus Ripple
V].
Check incoming power for a missing
phase or blown fuse. If drive is used
intentionally with single phase
input, apply output derating to 35%
actual drive rating.
F29
Analog Input
Loss
1
An analog input is configured to fault
on signal loss. A signal loss has
occurred.
Configure with
[Anlalog In
Loss].
1. Check parameters.
2. Check for broken/loose
connections at inputs.
F32
Fan Fdbck Loss
(FRN 6.xx and
later)
2
A loss of cooling fan feedback has
been detected. (Frames E and F only
Make sure cooling fans are clear of
debris and spinning freely. Replace
fan if necessary.
F33
Auto Rstrt Tries
2
Drive unsuccessfully attempted to
reset a fault and resume running for
the programmed number of
[Auto Rstrt Tries].
Correct the cause of the fault and
manually clear.
F38
Phase U to Gnd
2
A phase to ground fault has been
detected between the drive and
motor in this phase.
1. Check the wiring between the
drive and motor.
2. Check motor for grounded phase.
3. Replace drive if fault cannot be
cleared.
F39
Phase V to Gnd
F40
Phase W to Gnd
F41
Phase UV Short
2
Excessive current has been detected
between these two output terminals.
1. Check the motor and drive
output terminal wiring for a
shorted condition.
2. Replace drive if fault cannot be
cleared.
F42
Phase UW Short
F43
Phase VW Short
F48
Params
Defaulted
The drive was commanded to write
default values to EEPROM.
1. Clear the fault or cycle power to
the drive.
2. Program the drive parameters as
needed.
F63
SW OverCurrent
1
Programmed
has been exceeded.
Check load requirements and
[SW Current Trip] setting.
F64
Drive Overload
2
Drive rating of 110% for 1 minute or
150% for 3 seconds has been
exceeded.
Reduce load or extend Accel Time.
F70
Power Unit
2
Failure has been detected in the drive
power section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
F71
Net Loss
The communication network has
faulted.
1. Cycle power.
2. Check communications cabling.
3. Check network adapter setting.
4. Check external network status.
Table 18 - Fault Types, Descriptions and Actions
No.
Fault
Type
(1)
Description
Action
Содержание 22C-B012N103
Страница 8: ...6 Rockwell Automation Publication 22C UM001J EN E January 2017 Summary of Changes Notes...
Страница 46: ...44 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 1 Installation Wiring Notes...
Страница 56: ...54 Rockwell Automation Publication 22C UM001J EN E January 2017 Chapter 2 Start Up Notes...
Страница 154: ...152 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix B Accessories and Dimensions Notes...
Страница 176: ...174 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix E Modbus RTU Protocol Notes...
Страница 192: ...190 Rockwell Automation Publication 22C UM001J EN E January 2017 Appendix G P1 FloorLevel Network FLN Notes...
Страница 195: ......