160
Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix C
Configuration Reference Information
Table 69 - Test Output Parameters
Parameter Name
Value
Description
Default
Test Output Mode
Not Used
An external device is not connected.
Not Used
Standard
The output is connected to a standard device.
Pulse Test
A contact output device is connected. Use in combination with a safety
input.
Power Supply
The power supply of a Safety Sensor is connected. The voltage supplied to
I/O power (V, G) is output from the test output terminal.
Muting Lamp Output
1791ES-IB8XOBV4, 1732ES-IB8XOBV4,
1732ES-IB8XOB8 modules = T3 and T7
1791ES-IB16, 1732ES-IB16 modules = T3, T7,
T11, and T15
1732ES-IB12XOBV2, 1732ES-IB12XOB4
modules = T3, T7, and T11
An indicator is connected and turned ON to detect broken lines in an
external indicator.
Table 70 - Safety Output Parameters
Parameter Name
Value
Description
Default
Output Point Mode
Not Used
An external output device is not connected.
Not Used
Safety
When the output is ON, the test pulse is not output (remains ON).
Safety Pulse Test
By using this function, short circuits between output signal lines and the
power supply (positive side) and short circuits between output signal lines
can be detected.
Output Point Operation Type
Single Channel
(1)
Use as single channel.
Dual-channel
Dual-channel
Use as dual-channel. When both channels are normal, outputs can be
turned ON.
(1) 1732ES-IB12XOB4 and 1732ES-IB8XOB8 modules only.
Содержание 1732ES-IB12XOB4
Страница 6: ...6 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Summary of Changes Notes ...
Страница 38: ...38 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Chapter 2 About the Modules Notes ...
Страница 174: ...174 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Index Notes ...
Страница 175: ......