144
Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
Appendix A
Get Diagnostic Status from Modules by Using Explicit Messaging
See
for reference data related to input and output data.
Table 55 - Input Data 1732ES-IB16 Modules
Instance Hex
(decimal)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
205 (517)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9
Safety Input 8
225 (549)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9
Safety Input 8
2
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3
Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
300 (768)
Standard only
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Input Power
Error
315 (789)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9
Safety Input 8
2
Combined
Safety In
Status
Reserved
Input Power
Error
(1)
Reserved
Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
335 (821)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9
Safety Input 8
2
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3
Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4
Reserved
Reserved
Input Power
Error
Reserved
Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
365 (869)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input
15
Safety Input
14
Safety Input
13
Safety Input
12
Safety Input
11
Safety Input
10
Safety Input 9
Safety Input 8
2
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
3
Safety Input
15 Status
Safety Input
14 Status
Safety Input
13 Status
Safety Input
12 Status
Safety Input
11 Status
Safety Input
10 Status
Safety Input 9
Status
Safety Input 8
Status
4
Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
5
Test Output
15 Status
Test Output
14 Status
Test Output
13 Status
Test Output
12 Status
Test Output
11 Status
Test Output
10 Status
Test Output 9
Status
Test Output 8
Status
6
Reserved
Reserved
Input Power
Error
Reserved
Muting Lamp
15 Status
Muting Lamp
11 Status
Muting Lamp
7 Status
Muting Lamp
3 Status
385 (901)
Standard only
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Input Power
Error
1
Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
2
Test Output
15 Status
Test Output
14 Status
Test Output
13 Status
Test Output
12 Status
Test Output
11 Status
Test Output
10 Status
Test Output 9
Status
Test Output 8
Status
(1) This data is only diagnostic data. This data does not have safety integrity.
Содержание 1732ES-IB12XOB4
Страница 6: ...6 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Summary of Changes Notes ...
Страница 38: ...38 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Chapter 2 About the Modules Notes ...
Страница 174: ...174 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Index Notes ...
Страница 175: ......