Rockwell Automation Publication 1791ES-UM001G-EN-P - November 2016
145
Get Diagnostic Status from Modules by Using Explicit Messaging
Appendix A
Table 56 - Input Data 1732ES-IB8XOBV4 and 1732ES-IB8XOB8 Modules
Instance Hex
(decimal)
Connection Type
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
204 (516)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
224 (548)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
301 (769)
Only standard
0
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Output Power
Error
Input Power
Error
324 (804)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Combined
Safety In
Status
Combined
Safety Out
Status
Input Power
Error
(1)
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
334 (820)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2
Reserved
Reserved
Input Power
Error
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
344 (836)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2
Safety Output
7 Status
Safety Output
6 Status
Safety Output
5 Status
Safety Output
4 Status
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
3
Reserved
Reserved
Input Power
Error
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
354 (852)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2
Safety Output
7 Status
Safety Output
6 Status
Safety Output
5 Status
Safety Output
4 Status
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
3
Safety Output
7 Monitor
Safety Output
6 Monitor
Safety Output
5 Monitor
Safety Output
4 Monitor
Safety Output
3 Monitor
Safety Output
2 Monitor
Safety Output
1 Monitor
Safety Output
0 Monitor
4
Reserved
Reserved
Input Power
Error
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
364 (868)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2
Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output O
Status
3
Reserved
Reserved
Input Power
Error
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
374 (884)
Safety and standard
0
Safety Input 7
Safety Input 6
Safety Input 5
Safety Input 4
Safety Input 3
Safety Input 2
Safety Input 1
Safety Input 0
1
Safety Input 7
Status
Safety Input 6
Status
Safety Input 5
Status
Safety Input 4
Status
Safety Input 3
Status
Safety Input 2
Status
Safety Input 1
Status
Safety Input 0
Status
2
Safety Output
7 Status
Safety Output
6 Status
Safety Output
5 Status
Safety Output
4 Status
Safety Output
3 Status
Safety Output
2 Status
Safety Output
1 Status
Safety Output
0 Status
3
Safety Output
7 Monitor
Safety Output
6 Monitor
Safety Output
5 Monitor
Safety Output
4 Monitor
Safety Output
3 Monitor
Safety Output
2 Monitor
Safety Output
1 Monitor
Safety Output
0 Monitor
4
Test Output 7
Status
Test Output 6
Status
Test Output 5
Status
Test Output 4
Status
Test Output 3
Status
Test Output 2
Status
Test Output 1
Status
Test Output 0
Status
6
Reserved
Reserved
Input Power
Error
Output Power
Error
Reserved
Reserved
Muting Lamp
7 Status
Muting Lamp
3 Status
Содержание 1732ES-IB12XOB4
Страница 6: ...6 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Summary of Changes Notes ...
Страница 38: ...38 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Chapter 2 About the Modules Notes ...
Страница 174: ...174 Rockwell Automation Publication 1791ES UM001G EN P November 2016 Index Notes ...
Страница 175: ......