Calibration
47
16.5.3 8V to 12V Range
Shift+Serv|Password|Calibration|Voltage Channel | 8-12V Range
1)
From the Calibration menu, select Voltage Channel, then 8 - 12V range.
2)
Adjust the Cal source to 10.000 volts
100mV on the DVM.
3)
Press the Up/Down arrows until the voltage on the CRT matches the
DVM.
4)
Record the actual input and the CRT reading on the form.
5)
Press F2 Accept.
6)
From the Calibration menu, select Voltage Channel, 8 - 12V range.
7)
Linearity: Adjust the Cal source to 7.800V
100mV on the DVM and
record the actual input and CRT reading.
8)
Linearity: Adjust the Cal source to 13.200V
100mV on the DVM and
record the actual input and CRT reading.
9)
Press F3 Cancel.
16.5.4 16V Range
Shift+Serv|Password|Calibration|Voltage Channel | 16V Range
1)
From the Calibration menu, select Voltage Channel, then 16V range.
2)
Adjust the Cal source to 17.500 volts
100mV on the DVM.
3)
Press the Up/Down arrows until the voltage on the CRT matches the
DVM.
4)
Record the actual input and the CRT reading on the form.
5)
Press F2 Accept.
6)
From the Calibration menu, select Voltage Channel, 16V range.
7)
Linearity: Adjust the Cal source to 15.200V
100mV on the DVM and
record the actual input and CRT reading.
8)
Linearity: Adjust the Cal source to 19.200V
100mV on the DVM and
record the actual input and CRT reading.
9)
Press F3 Cancel.
10)
Remove the DVM leads from points A and B.
11)
Set the Cal source to 0 volts.