Calibration
45
16.3 Recording the As Found K-Constants
Shift+Serv|Password|Calibration|Cal-K|
Record the before-calibration K-Constants onto the Calibration Form. To
display the constants, from the Calibration menu, press F2 Cal-K. Press the
Up/Down arrows to display three screens of K-constants. Record these
values in the Calibration Form K-Constant Before Cal column. When
finished, press Cancel.
16.4 Voltage Channel Setup
To calibrate the Voltage Channel, connect the Cellcorder voltage leads and
calibration source power supply as shown in the following figure.
Figure 23. Voltage Channel Setup
1)
With the Calibration (Cal) source at 0 volts, connect the DVM to points
A and B at the Cal source.
2)
Calibrate the four voltage ranges as follows.
16.5 Voltage Channel Calibration
Shift+Serv|Password|Calibration|Voltage Channel |
select voltage range
The following four sections describe voltage calibration.
NOTE: If Linearity tests fail to meet min/max range, do not adjust the
Up/Down arrow keys. You must recalibrate the initial setting where you
used the arrow keys, then retest linearity.
Figure 24. Voltage Channel Menus
Calibration
Source
Power Supply
CRT-300
Cellcorder
Red Clamp
A
( + )
Black Clamp
B
( – )
Содержание Cellcorder CRT-300