Calibration
50
16.7.3 8V to 12V Load (
I3
)
Shift+Serv|Password|Calibration|Test
I
Channel | 8 - 12V Load
Current for this load test depends on the flash code version, as described at
the start of this section. If the flash version has no asterisk ( * ), such as
02.00A08, set the Cal source so the DVM indicates 16 to 17mV. If the code
has an asterisk, such as 02.00A08*, set the Cal source to 31 to 32mV.
1)
From the Calibration menu, select Test I Channel, then 8 - 12V Load.
2)
Press F1 Start.
3)
Adjust the Cal source to 16 to 17mV or 31 to 32mV on the DVM.
4)
Press F1 Start.
5)
Press the Up/Down arrows until the test current on the CRT matches the
DVM.
6)
Record the actual input and the CRT reading on the form.
7)
Press F2 Accept.
16.7.4 16V Load (
I4
)
Shift+Serv|Password|Calibration|Test
I
Channel | 16V Load
1)
From the Calibration menu, select Test I Channel, then 16V Load.
2)
Press F1 Start.
3)
Adjust the Cal source to 6.1 to 6.4mV on the DVM.
4)
Press F1 Start.
5)
Press the Up/Down arrows until the test current on the CRT matches the
DVM.
6)
Record the actual input and the CRT reading on the form.
7)
Press F2 Accept.
8)
Remove the DVM leads from points C and D.
9)
Set the Cal source to 0 volts.