53
A. In cooling, when the outdoor lower than the indoor, or in heating the outdoor higher than
the indoor, the compensation factor use the curve value minus the following table value
6.3 Capacity compensation value for cooling and heating
B. Capacity compensation suitable for outdoor outlet static pressure
Outdoor outlet static pressure
(
Pa
)
0
10
20
30
40
50
60
70
80
Adjustment coefficient
1
1
0.99
0.98
0.97
0.96
0.95
0.94
0.93
The vertical height difference between indoor and outdoor unit
5m 10m 15m 20m 25m 30m 35m 40m 45m 50m
Adjustment coefficient
0.99 0.98 0.97 0.96 0.95 0.94 0.93 0.92 0.91 0.90