Failure code
Outdoor
digital
display tube:
110-0, 1, 1
Indoor wired
controller:
6E
Indoor unit LED status
LED5
Failure description:
Overcurrent of module 1 and 2
20 times
Outdoor unit LED status
LED1
LED2
Normal
Normal
1. Model
Failure diagnosis and troubleshooting
Flow Logic III series
Diagnosis
Troubleshooting
2. Abnormity detection method
◆
Check if the modules are in
normal conditions and if P and
N are short-circuited to U, V
and W.
◆
Check if the modules are
fixed securely and the heat
dissipation is good;
◆
Check if the compressor
resistance is normal,
◆
Check if the compressor
wiring UVW is wrongly
connected and if the inverter
board and module board are
wired securely.
3. Abnormity confirmation
conditions
Overcurrent of module hardware
4. Possible causes
◆
The module alarms FO
failure due to poor heat
dissipation;
◆
The module alarms failure
as it is broken down;
◆
Liquid shock is found in
compressor, which results in
overcurrent upon starting or
operating;
◆
The winding resistance of
compressor is large;
◆
UVW wiring is wrongly
connected or the inverter board
and module board are wired
insecurely.
Check if the supply voltage is normal
Check if the electrical cabinet and
compressor wires are secured, the
UVW is correctly connected and
the variable frequency board and
module board are wired correctly.
Check if the power module is normal
Check if there is other failure,
112, 113 and 114
Check if the compressor, resistance
and insulation are normal
Troubleshoot each failure.
Rectify on site by after-sales
personnel.
Rectify on site by after-sales
personnel.
Replace on site by after-sales
personnel.
Replace the compressor.
Detect by exclusion.
Y
Y
Y
Y
Y
N
N
N
N
N
Содержание AWAU-YDV1010-H13
Страница 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Страница 56: ...54 7 Operation range...
Страница 102: ...100 Power module driver board 0151800090B and 0151800090...
Страница 103: ...101 Filter board MHW505A012...
Страница 187: ...Airwell reserves the right to make change without any notice...