111
Dip switch setting condition of PCB board is displayed when SW9 is 15.
SW9
SW10
SW11
Functions
Operation methods
15
0
2
Setting condition of BM1 and BM2
Hexadecimal display, BM1: indicating by LED1
and LD2, BM2: indicating by LED3 and LED4
15
1
2
Setting condition of BM3 and BM4
Hexadecimal display, BM3: indicating by LED1
and LED2, BM4: indicating by LED3 and LED4
15
2
2
Capacity correction level
0 indicates that the pipe is short; 1 indicates
the pipe length is moderate; 2 indicates that the
pipe is long.
15
3
2
Defrosting compensation α
10, 8, 6
15
4
2
Power damping (the maximum
output is allowable)
100 indicates 100%, and 0 indicates output is
forbidden
15
5
2
Capacity overload detection
135 indicates there is limit, and 0 indicates there
is no limit
15
6
2
Heating limit when external air is
more than 25 °C
25 indicates there is limit, and 0 indicates there
is no limit
15
7
2
Setting of mute operation
0 indicates non-mute operation, and 1 indicates
mute operation
15
8
2
Setting of anti-snow operation
0 indicates the operation without snow
prevention, and 1 indicates the operation with
snow prevention
15
9
2
Operation setting of wind speed of
sub-unit FAN of ThermoOff during
operating of heating main unit
0 indicates there is no operation, and 1 indicates
there is operation
15
10
2
Insignificance
Insignificance
15
11
2
High head setting
0 indicates invalidity, 1 indicates high head
above outdoor unit and 2 indicates high head
under outdoor unit.
15
12
2
Setting of 50 Hz and 60 Hz power
supply detection
50 indicates 50 Hz, and 60 indicates 60 Hz
15
13
2
Reservation
Reservation
15
14
2
Type setting of outdoor unit
0 indicates AV*NMMEUA model, 1 indicates
sideward air outlet model, and 2 indicates five-
in-one model
15
15
2
Reservation
Reservation
Outdoor unit valve manual control
SW9
SW10 SW11
Functions
Operation methods
6
15
2
Cancel all the manual controls
(component type)
• Press SW2 (UP) for 2s continuously, display
1111, then to quit, or press SW1 (DOWN) for 2s
continuously, display 0000, then quit the set.
• Cancel items:
Movable component control by hand such as
compressor, motor, electronic expansion valve
(LEV), solenoid valve (SV) and so on (including
evacuation and charging; excluding rated
operation, compulsory operation, indoor run/stop,
etc.)
Содержание AWAU-YDV1010-H13
Страница 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Страница 56: ...54 7 Operation range...
Страница 102: ...100 Power module driver board 0151800090B and 0151800090...
Страница 103: ...101 Filter board MHW505A012...
Страница 187: ...Airwell reserves the right to make change without any notice...