82
1. Wiring system diagram
(Combined unit)
Outdoor unit power supply three-phase 380V
Outdoor unit
Indoor unit
Wired
controller
Indoor unit power supply single-phase 220V
Leakage circuit
breaker
(non-operational
shock wave type)
Line circuit
breaker
Line circuit
breaker
Ground wire
Leakage circuit
breaker
A: Power supply wire (main power supply wire) [4-core]
B: Signal wire (outdoor-outdoor Signal wire) [3-core]
C: Signal wire (hyper connected wire) [2-core]
D: Power supply wire (indoor power supply wire) [2-core]
E: Wired controller wire [3-core]
Note: In case leakage protector is exclusive for ground protection, another protector shall be set for wiring.
2. Essentials in power supply wire connection
(1) Wire removal method
• As shown in Figure 2-(1) in Page 16, the wire can be removed from the front, the right, the left and the
bottom.
• When connecting the wire on site, please cut off the semi-finished through hole on the outer plate by a
wrench (hole of Ø50mm or slot hole of 40mm×80mm dimension)
(2) Attentions during connection of power supply wires
Power supply wires should be connected to power supply wiring board and fixed outside electrical box.
When connecting to power supply wiring board, please use rounded compression joint.
• Ground wires should be connected before connection of power supply wire. Besides, when connected to
the terminal board, the ground wire should be longer than the power supply wire and be free from bearing
tension.
• Never connect power supply before completion of the works. Conduct maintenance after cutting off the
power supply.
B
Содержание AWAU-YDV1010-H13
Страница 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Страница 56: ...54 7 Operation range...
Страница 102: ...100 Power module driver board 0151800090B and 0151800090...
Страница 103: ...101 Filter board MHW505A012...
Страница 187: ...Airwell reserves the right to make change without any notice...