110
SW9
SW10 SW11
Function
Operation methods
0
9
2
Refrigerant charging setting
*only for gas charged outdoor. If indoor
is charged, do not set. Note: When
it finishes, cancel the setting or re-
electricity.
• Press SW2 (UP) for 2s continuously, display
1111 and start up; digital tube displays “YES”.
■ Specific action: LEVa1 and 2 open for 470
Pls, the other valves close
compulsorily, and SV21 open and LEVc open
for 470.
• Press SW1 (DOWN) for 2s continuously,
display 0000 and stops (setting is invalid when
unit is running.)
0
10
2
Wrong wiring inspection in cooling
• Press SW2(UP) for 2s continuously, display
1111 and start up; digital tube counts down
judging time at second; after time arrives,
display the result:
■ “00.00” shows the result is in conformity with
the actual connection;
■ “01.05” shows one outdoor and 5 indoors are
abnormal,
To check the abnormal units by digital tube
(indoor: X_X_12; outdoor: X_0_0);
• Press SW1 (DOWN) for 2s continuously,
display 0000, and stops.
0
11
2
Operation detection in case of heating
false wiring
0
12
2
Indoor expansion valve open fully
Press SW2 (UP) for 2s continuously, display
1111 and indoor valves open fully for 2 minutes,
then indoor valves close automatically.
0
13
2
All indoor units running in cooling
• Press SW2(UP) for 2s continuously, display
1111, and start up;
• Press SW1 (DOWN) for 2s continuously,
display 0000, and stops.
0
14
2
All indoor units running in heating
0
15
2
Cancel all manual controls (running
type)
• Press SW2(UP) for 2s continuously,
display 1111 and start up, then cancel the
manual control; or press SW1(DOWN) for 2s
continuously, display 0000 and then cancel the
manual control;
• Cancel items:
Wrong wiring inspection in cooling/ heating
mode; indoor running/stop totally; compulsory
operation; rated operation, etc.
Содержание AWAU-YDV1010-H13
Страница 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Страница 56: ...54 7 Operation range...
Страница 102: ...100 Power module driver board 0151800090B and 0151800090...
Страница 103: ...101 Filter board MHW505A012...
Страница 187: ...Airwell reserves the right to make change without any notice...