105
Monitor tools
According to the dip switch code comparison table of outside unit, adjust SW9, SW10 and SW11 and observe
operation parameters of the unit, and then record the parameters in the form of operation and commissioning.
The displayed contents are defined as follows:
• Buttons: SW2 (UP) and SW1 (DOWN)
• Dip switch panel: SW9, SW10 and SW11: they are settable dip switches from 0 to 15
• Displayed part: LED1, LED2, LED3 and LED4: the four digital tubes arranged from left to right.
1)Parameter observation of indoor unit
SW9 and SW10 indicate number of indoor unit, and SW11 indicates parameter description of indoor unit.
SW9
SW10
Indoor unit address
0
0-15
1-16
1
17-32
2
33-48
3
49-64
SW11
Functions
Digital tube SMG1 and SMG2 display
3
Indoor unit program version
If communication is normal, show the indoor unit program version
(one decimal). If communication stops, normally show “0000” (failing
communication for 5 consecutive rounds). If communication has been
abnormal, show “----”.
For example,“F0.1” means indoor unit version is V0.1
4
Indoor abnormal
Display indoor failure code; no failure, display 0
5
Indoor capacity
Indoor capacity (Unit: W, a decimal),1.5 HP displays 1.5
6
Indoor EEV open angle
Electronic expansion valve (EEV) open angle (Unit: Pls)
7
Indoor ambient temp. “Tai”
Ambient temperature (Unit: °C)
8
Indoor gas pipe temp. “Tc1” Gas pipe temperature (Unit: °C)
9
Indoor liquid pipe temp. “Tc2” Liquid pipe temperature (Unit: °C)
10
Startup mode, actual
operating wind speed and
capacity code of indoor unit
LED1 shows startup mode such as O: Shutdown C: cooling H: Heating
LED2 indicates actual operating wind speed of indoor unit (0 - stop, 1 - low
wind, 2 - medium wind and 3 - high wind)
LED3 and LED4 indicate capacity code (0~15).
For example, C311 indicates cooling operating at high wind, and the
capacity is 11.
11
Setting temperature “Tset” of
indoor unit
Setting temperature (Unit: °C)
12
Wrong wiring inspection
0 shows no failure, 79 shows wiring connection failure (indoor no display)
13
Forced startup & shutdown
of indoor unit for cooling
• Hold down SW2 (UP) for 2 seconds until 1111 is displayed, it means
startup
14
Forced startup & shutdown
of indoor unit for heating
• Hold down SW1 (DOWN) for 2 seconds until 0000 is displayed, it means
shutdown
Содержание AWAU-YDV1010-H13
Страница 1: ...SYJS 03 2017 REV A Edition 2017 03 Service Manual Flow Logic III...
Страница 56: ...54 7 Operation range...
Страница 102: ...100 Power module driver board 0151800090B and 0151800090...
Страница 103: ...101 Filter board MHW505A012...
Страница 187: ...Airwell reserves the right to make change without any notice...