Electrical installation
GasEye Cross Duct
Operating instructions, 05/2021
81
Industrial protocols connection
The GasEye Cross Duct gas analyzer has implemented MODBUS RTU, MODBUS
TCP and PROFINET industrial communication protocols. On plant can work only one
protocol and it is declared by customer during ordering. Thanks to integrated analyzer
software and electronic board with Anybus CompactCom communication module
device is very flexible and for special customer requirement additional communication
protocols can be quickly implemented.
Modbus RTU (RS485)
Modbus RTU is fully implemented by Airoptic and does not need additional
communication module. Device can work in slave mode. Communication parameters
are configured by Analyzer web server tool.
Figure 91. Location RS-485 socket on Analyzer PCB Host 4.X.
1. RS-485 transmission settings
Baud rate: 9600/19200
Stop bits: STOP_BIT_1/ STOP_BIT_2
Parity:
NO_PARITY_8_BIT/
EVEN_PARITY_8_BIT/
ODD_PARITY_8_BIT/
NO_PARITY_9_BIT
Flow control: none
2. Modbus byte transmission method
Byte Order: LSB/MSB
Swap: ON/OFF
3. Device Address
Modbus slave device address from 1 to 247 are shown in the Table 7 below.
Содержание GasEye
Страница 1: ......
Страница 2: ...Introduction 2 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 4: ...Introduction 4 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 8: ...Introduction 8 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 21: ...Technical data GasEye Cross Duct Operating instructions 05 2021 21 Figure 8 Calibration certificate...
Страница 188: ...WebServer application 188 GasEye Cross Duct SG and MG Operating instructions 05 2021 Figure 180 Alarm parameters window...