Electrical installation
52
GasEye Cross Duct SG and MG
Operating instructions, 05/2021
Power supply
Specification
Device requirements:
voltage range: 19÷30 VDC, typ. 24 VDC,
power consumption: max. 15W / 25W (single / multi gas device).
For proper operation of the device secure adequate power supply.
Connection
Connect the power supply to HOST board P3 terminal. Use the customer cable
provided with the device or use a standard cable (shielded cable is preferred) with a
maximum wire diameter of 2.5 mm
2
(14AWG). Connect the positive pole of the power
supply to the pin 25 and negative pole to the pin 26. Power supply connection diagram
is presented at Figure 50.
Figure 50. Power supply connection diagram.