Electrical installation
108
GasEye Cross Duct SG and MG
Operating instructions, 05/2021
0x45
69 16 -bits of floating point value
(second part)
Manual mode value in scaling
range
AOUT2.SCALE_MIN
0x46
70 16 -bits of floating point value (first
part)
Scaling range value corresponds to
4 mA
0x47
71 16 -bits of floating point value
(second part)
Scaling range value corresponds to
4 mA
AOUT2.SCALE_MAX
0x48
72 16 -bits of floating point value (first
part)
Scaling range value corresponds to
20 mA
0x49
73 16 -bits of floating point value
(second part)
Scaling range value corresponds to
20 mA
AOUT2.A
0x4A
74 16 -bits of floating point value (first
part)
Reserved - future use
0x4B
75 16 -bits of floating point value
(second part)
Reserved - future use
AOUT2.B
0x4C
76 16 -bits of floating point value (first
part)
Reserved - future use
0x4D
77 16 -bits of floating point value
(second part)
Reserved - future use
AOUT3.SELECT_SIGNAL
0x4E
78 Measurement signal selection for
the output
AOUT3.MANUAL_VALUE
0x4F
79 16 -bits of floating point value (first
part)
Manual mode value in scaling
range
0x50
80 16 -bits of floating point value
(second part)
Manual mode value in scaling
range
AOUT3.SCALE_MIN
0x51
81 16 -bits of floating point value (first
part)
Scaling range value corresponds to
4 mA
Содержание GasEye
Страница 1: ......
Страница 2: ...Introduction 2 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 4: ...Introduction 4 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 8: ...Introduction 8 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 21: ...Technical data GasEye Cross Duct Operating instructions 05 2021 21 Figure 8 Calibration certificate...
Страница 188: ...WebServer application 188 GasEye Cross Duct SG and MG Operating instructions 05 2021 Figure 180 Alarm parameters window...