ATEX (Zone 1 and 21 purging system
installation)
GasEye Cross Duct
Operating instructions, 05/2021
227
System conservation for zone 1 and 21
In order to insure safe and convenient operating conditions of 6500-type purging
system, subsequent requirements must be satisfied:
-
Inlet pressure of the gas must not exceed 2 bar
-
Vent pressure reading on the controller display must not exceed 24mbar.
-
An ATEX certified manometer should be installed right after solenoid valve for
inlet pressure monitoring
-
Temperature of the inlet gas must not exceed 40
o
C
-
External parts made of plastic should be cleaned with a damp cloth, with the
addition of antistatic fluids
-
All metal parts of the system must be grounded
-
System must not be exposed to UV light sources and direct sunlight
-
When servicing, installing, and commissioning, the area must be free of all
combustible material and/or hazardous explosive gas
-
Only the terminal compartment of the control unit is accessible to users. Under
no circumstances shall the control unit, manifold or vent be dismantled or
removed from the supplied enclosure
-
In case of any system failure, please contact Airoptic Sp. z o.o.
Contact information
Airoptic Sp. z o.o.
ul. Rubiez 46B
61-612 Poznan, Poland
www.airoptic.pl
tel. +48 61 6272128
fax.+48 61 6272129
Содержание GasEye
Страница 1: ......
Страница 2: ...Introduction 2 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 4: ...Introduction 4 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 8: ...Introduction 8 GasEye Cross Duct SG and MG Operating instructions 05 2021...
Страница 21: ...Technical data GasEye Cross Duct Operating instructions 05 2021 21 Figure 8 Calibration certificate...
Страница 188: ...WebServer application 188 GasEye Cross Duct SG and MG Operating instructions 05 2021 Figure 180 Alarm parameters window...