INSTALLER - Remote control - Connection with BMS settings
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the address associated with the AER485P1 board (not supplied) connected to the
Multichiller-Evo pCO5+ board to communicate with an external BMS system;
2
Indicates the type of protocol used to communicate with the BMS system; this protocol can be:
CAREL
= Carel property protocol;
MODBUS EXTENDED
= Modbus extended protocol;
WINLOAD
= communication via winload;
3
Indicates the communication speed for connection with the BMS;
4
Indicates the number of stop bits used in the communication protocol with the BMS;
5
Indicates the type of parity used in the communication protocol with the BMS;
ACTIONS
AVAILABLE:
1
A
B
C
2
3
4
5
Go to next page;
Go to alarms menu;
D
E
F
G
H
D
E
F
Allows setting the address of the AER485P1 serial
board (not supplied);
Allows selecting the protocol to be used in the
communication with the BMS;
Allows setting the serial communication speed
with the BMS;
G
H
Allows selecting the number of stop bits to be
used in the communication with the BMS;
Allows setting the type of serial communication
parity with the BMS;
INSTALLER - Remote control - Changeover management
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the type of changeover management type; this management can be:
COOLING ONLY
= the chillers do not provide for the heating function so the system is set for
cooling management only;
FROM TOUCH
= the changeover between heating and cooling is allowed through the touch screen
interface;
FROM DIG. INP. ID1
= the changeover is managed by the ID1 digital input on the pCO5+ board;
FROM BMS
: the season change is managed via remote control from BMS;
2
Indicates (if you have chosen to manage the changeover via digital input ID1) which input status to
associate with the cooling mode (open or closed);
3
Indicates the current functioning mode set for the system;
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
Allows you to select the changeover manage-
ment to be applied to the system;
Allows selecting the management logic of the
ID1 digital input;
C
3
F
E
Go back to previous page;