34
INSTALLER - Remote control - Power demand/limitation settings (U2 set as NTC probe)
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart representing the power demand or limitation (if selected as function on the U2
input, with temperature variation) according to the temperature read by the NTC probe connected
to the U2 input; the chart shows the temperature at which no chiller is active, and the one at which
to activate the maximum number of chillers specified for the cooling mode
2
Indicates the chart representing the power demand or limitation (if selected as function on the U2
input, with temperature variation) according to the temperature read by the NTC probe connected
to the U2 input; the chart shows the temperature at which no chiller is active, and the one at which
to activate the maximum number of chillers specified for the heating mode
3
It summarises the current system state, indicating the active functioning mode, the temperature
read by the NTC probe connected to the U2 input and the maximum number of chillers that can be
activated at that time
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
Allows setting up to which temperature no chiller
will be activated (cooling);
Allows setting at which temperature the speci-
fied number of chillers will be activated;
C
Go back to previous page;
3
G
Allows setting the maximum number of chillers
that can be activated;
G
E
F
L
H
I
H
I
Allows setting up to which temperature no chiller
will be activated (heating);
Allows setting at which temperature the speci-
fied number of chillers will be activated;
L
Allows setting the maximum number of chillers
that can be activated;
INSTALLER - Remote control - Power demand/limitation settings (U2 set as voltage or current value)
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart representing the power demand or limitation (if selected as function on the U2
input, with voltage or current signal) according to the U2 input signal value; the chart shows the
values at which no chiller is active, and those at which to activate the maximum number of chillers
specified for the cooling mode
2
Indicates the chart representing the power demand or limitation (if selected as function on the U2
input, with voltage or current signal) according to the U2 input signal value; the chart shows the
values at which no chiller is active, and those at which to activate the maximum number of chillers
specified for the heating mode
3
It summarises the current system state, indicating the active functioning mode, the U2 input signal
value and the maximum number of chillers that can be activated at that time
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
C
Go back to previous page;
3
Allows setting the maximum number of chillers
that can be activated in cooling at the maximum
of the input signal;
E
F
Allows setting the maximum number of chillers
that can be activated in heating at the maximum
of the input signal;