16
ON/OFF - Main functioning settings - TIME PERIODS sub-menu - Daily setting
A
B
C
Go back to the On/Off menu;
Go to next page;
Go to alarms menu;
Index
Meaning
1
Indicates the day to which the displayed time settings refer
2
Indicates the start times for the time periods (each day can have up to four)
3
Indicates the end times for the time periods (each day can have up to four)
4
Indicates the action to be associated with each time period (each day can have up to four); the
possible actions can be:
OFF = during the specified time period the system chillers will be off;
SET1 = during the specified time period the chillers will be on with the main set;
SET2 = during the specified time period the chillers will be on with the secondary set;
ACTIONS
AVAILABLE:
D
E
F
Select the day of the week to be set;
Set the start time (divided by hours and minutes)
of the first time period;
Set the end time (divided by hours and minutes)
of the first time period;
G
Set the action to be performed during the first
time period;
H
I
Set the start time (divided by hours and minutes)
of the second time period;
Set the end time (divided by hours and minutes)
of the second time period;
L
Set the action to be performed during the se-
cond time period;
M
N
Set the start time (divided by hours and minutes)
of the third time period;
Set the end time (divided by hours and minutes)
of the third time period;
O
Set the action to be performed during the third
time period;
P
Q
Set the start time (divided by hours and minutes)
of the fourth time period;
Set the end time (divided by hours and minutes)
of the fourth time period;
R
Set the action to be performed during the fourth
time period;
1
A
C
D
E
2
4
3
F
B
G
L
O
R
H
I
M
N
P
Q
Содержание Multichiller-Evo