29
INSTALLER - Thresholds and timing - Chiller ignition Priority/Order settings for fixed threshold management
A
B
D
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the priority index assigned to the chiller (n) both cooling and heating; the lower the index
the higher the chiller priority during ignition; if two or more chillers have the same priority index, the
one with the least number of worked hours will have priority (in order to balance them); the logic
is reversed during switch-off, starting to switch-off the chiller with the higher index (if more chillers
have the same index, the one with the highest number of worked hours will switch-off first);
ACTIONS
AVAILABLE:
A
C
D
Go back to previous page;
Go to alarms menu;
Set the cooling priority of the chillers;
E
F
B
C
Go to next page;
Set the cooling heating priority of the chillers;
INSTALLER - Thresholds and timing - Backup chiller settings
A
B
D
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the possible chiller used as backup; if one of the system chillers is indicated as backup, said
chiller will always be off, automatically activating it if another chiller is locked by a serious alarm;
ACTIONS
AVAILABLE:
A
C
D
Go back to previous page;
Allows to set a possible backup chiller;
B
C
Go to alarms menu;
1
1
1
E
F
E
F