35
INSTALLER - Remote control - Recovery side set point compensation settings
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart that summarises the functioning of the climatic curve applied to the recovery
side set; setting at which outdoor air temperature (read by the NTC probe connected to the multi-
function input duly set) the recovery work set remains unchanged and at which it is decreased and
by how much
2
Indicates the chart that summarises the functioning of the climatic curve applied to the recovery
side set; setting the decrease to be applied to the heating set at maximum of the input signal
3
Indicates the value read by the device connected to input U3 and the set resulting from correction
according to the curve described
ACTIONS
AVAILABLE:
1
A
B
D
2
Go to next page;
Go to alarms menu;
D
E
F
Allows setting at which outdoor air temperature
to use the primary recovery side set;
Allows setting at which outdoor air temperature
to lower the primary recovery side set;
C
Go back to previous page;
3
G
Allows setting the decrease to be applied to the
recovery side set for the indicated temperature;
G
E
F
H
H
Allows setting the decrease to be applied to the
heating set at the maximum of the input signal;
INSTALLER - Remote control - Power demand/limitation settings on recovery side
A
B
C
Go back to the submenu selecting page;
Index
Meaning
1
Indicates the chart representing the power demand or limitation (if selected as function on the U3
input, with temperature variation) according to the temperature read by the NTC probe connected
to the U3 input; the chart shows the temperature at which no chiller is active, and the one at which
to activate the maximum number of chillers specified for the recovery mode
2
Indicates the chart representing the power demand or limitation (if selected as function on the U3
input, with voltage or current signal) according to the U3 input signal value; the chart shows the
values at which no chiller is active, and those at which to activate the maximum number of chillers
specified for the recovery mode
3
Indicates the value read by the device connected to input U3 and the maximum number of chillers
that can be activated at that time
ACTIONS
AVAILABLE:
1
A
B
C
2
Go to alarms menu;
D
E
F
Allows setting up to which recovery temperature
no chiller will be activated;
Allows setting at which temperature the speci-
fied number of chillers will be activated;
Go back to previous page;
3
G
Allows setting the maximum number of chillers
that can be activated;
F
D
E
G
Allows setting the maximum number of chillers
that can be activated at the maximum of the in-
put signal;