22
Ground Resistance Tester Model 6471
Measurement of auxiliary electrodes R
ρ
-
H
, R
ρ
-
S
, R
ρ
-
ES
, R
ρ
-
E
Measurement
Range
0.14 to
9.99
Ω
10.0 to
99.9
Ω
100 to
999
Ω
1.00 to
9.99k
Ω
10.0 to
99.9k
Ω
Resolution
0.1
Ω
0.1
Ω
1
Ω
10
Ω
100
Ω
Operating error
± (10% + 2cts)
The
START
button must be pressed for more than 2 s. For frequencies between
41 and 128Hz, the resistance of the auxiliary earth electrodes is measured at the
test frequency set. At higher frequencies the resistance is measured at 128Hz.
3.2.7 Earth/Ground Measurements with 2 Clamps
Measuring method:
Voltage/Current measurement with a rectangular AC signal
Induced short circuit current:
< 26Arms (with SR182) < 5Arms (with MN82)
Signal frequency:
Automatic: 1611Hz - Manual: 128, 1367, 1611 or 1758Hz
Noise suppression:
> 80 dB at frequencies differing by 20% or more from the
test frequency
Max. interfering current:
20A
peak
Max. value for R
H
, R
S
:
100k
Ω
Measuring time:
approx. 7 s for the first value of R
Loop
, then 3 meas. per s.
Measurement Range
0.10 to 9.99
Ω
10.0 to 99.9
Ω
100 to 500
Ω
Measurement frequency
1367Hz - 1611Hz - 1758Hz
Resolution
0.01
Ω
0.1
Ω
1
Ω
Operating error
(1)
(without external current)
SR182
± (10% + 1cts)
MN82
± (20% + 2cts)
Measurement Range
0.10 to 9.99
Ω
10 to 30
Ω
Measurement frequency
128Hz
Resolution
0.01
Ω
0.1
Ω
Operating error
(1)
(without external current)
SR182
± (20% + 2cts)
MN82
not specified
(1): Observe the minimum distance between the two clamps according to table in § 5.7.
3.3 Data Storage
Memory Capacity:
512 test results (64kB)
Communication:
Optically isolated USB
www.
ShopAEMC
.com
Shop for AEMC products online at:
1.888.610.7664