44
Ground Resistance Tester Model 6471
Observe the following minimum distances between the two clamps in order to
avoid direct electromagnetic influences between the transmitting clamp and the
receiving clamp:
Value measured
(
Ω
)
Minimum separation
MN82
SR182
0 to 1
0.1m (4")
0m (0")
1 to 5
0.4m (1' 04")
0.1m (4")
5 to 10
0.5m (1' 08")
0.2m (8")
10 to 50
0.7m (2' 04")
0.3m (1')
50 to 100
0.9m (3')
0.5m (1' 08")
100 to 500
1.2m (4')
0.5m (1' 08")
1.
Start the measurement by pressing the
START/STOP
button.
In the case of the diagram below, the earth impedance measured is equal to:
R
LOOP
= R
E
+ ( R
E1
// R
E2
// R
E3
)
> 2s
AUTO
Ω
Hz
H
ES
m A
NOTE:
In the AUTO mode, the measurement frequency is 1611Hz. To make
an earth measurement that is free of inductive effects, you must change to
MANUAL mode and choose a lower measurement frequency (see §6.2).
www.
ShopAEMC
.com
Shop for AEMC products online at:
1.888.610.7664