Ground Resistance Tester Model 6471
75
CHAPTER 10
TROUBLESHOOTING
10.1 Error Reporting
10.1.1 Electrode Resistance Too High
This can happen in a 3- or 4-pole earth measurement, a resistivity measurement,
or an earth potential measurement.
This message is displayed when the measurement is triggered by a short press of
the
START/STOP
button and the resistances of the auxiliary electrodes are too high.
The measurement must then be started by a long press on the
START/STOP
but
-
ton. The device then measures the values of the electrodes and compensates for
them to display the correct result.
10.1.2 Out of Range
<
>
or
The flashing > or < symbol indicates the measurement is
out of range.
<
>
and
If both symbols flash together, it means that the accuracy
of the value displayed is outside of the instrument
specification or is subject to large fluctuations. Activating
the smoothing function (SMOOTH) may correct this.
Press the
2nd
button, then the
SMOOTH
button to activate
smoothing.
10.1.3 Misconnection
H
S
ES
E
This flashing indicates that a terminal or a
current clamp needs to be either connect
-
ed or disconnected. You must correct the
connections or the measurement will not
proceed. The flashing of terminal H may
also indicate that current I
H-E
is too low. The
flashing of terminal S may also indicate that
resistance R
S
is too high. The flashing of
terminal ES may also indicate that the cur
-
rent I
ES
measured by the clamp is too low.
www.
ShopAEMC
.com
Shop for AEMC products online at:
1.888.610.7664