Ground Resistance Tester Model 6471
3-Pole earth resistance measurement R
E
Measurement
Range
0.09 to
9.99
Ω
10.0 to
99.9
Ω
100 to
999
Ω
1.00 to
9.99k
Ω
10.0 to
99.9k
Ω
Resolution
0.01
Ω
0.1
Ω
1
Ω
10
Ω
100
Ω
Intrinsic error
± (2% + 1ct)
Operating conditions: R
E
< 3 x R
H
, U
OUT
= 32V
Operating error for R
E
Values for R
H
, R
S
and R
E
Frequency (Hz)
(R
H
+ R
S
) / R
E
< 3000
R
H
≥
0
Ω
, Rs
≤
3k
Ω
41 to 513
± (3% + 2cts)
R
H
> 3k
Ω
, Rs
≤
30k
Ω
41 to 513
± (10% + 2cts)
(R
H
+ R
S
) / R
E
< 5000
R
H
> 30k
Ω
, Rs < 100k
Ω
41 to 128
± (10% + 3cts)
Note:
For a test voltage U
OUT
of 16V, halve the value for R
H
.
4-Pole earth resistance measurement R
E
Measurement
Range
0.01 to
9,999
Ω
10.00 to
99.99
Ω
100.0 to
999.9
Ω
1.000 to
9.999k
Ω
10.00 to
99.99k
Ω
Resolution
0.001
Ω
0.01
Ω
0.1
Ω
1
Ω
10
Ω
Intrinsic error
± (2% + 1ct)
Operating conditions: R
E
< 3 x R
H
, U
OUT
= 32V
Operating error for R
E
Values for R
H
, R
S
and R
E
Frequency (Hz)
(R
H
+ R
S
) / R
E
< 3000
R
H
≥
0
Ω
, Rs
≤
3k
Ω
41 to 513
± (3% + 2cts)
R
H
> 3k
Ω
, Rs
≤
30k
Ω
41 to 513
± (10% + 2cts)
(R
H
+ R
S
) / R
E
< 5000
R
H
> 30k
Ω
, Rs < 100k
Ω
41 to 128
± (10% + 3cts)
Note:
With a test voltage U
OUT
of 16V, halve the value of R
H
.
Selective 4-Pole earth resistance measurement with SR182 or MN82 clamp
Same characteristics as 4-Pole earth measurements with the following particular
conditions:
Minimum current:
SR182, I
ES
>0.5mA
MN82, I
ES
>2mA
Maximum R
SEL
/R
E
ratio: SR182, (R
SEL
/R
E
) <500
MN82, (R
SEL
/R
E
) <120
with R
H
+ R
E
<20
Ω
www.
ShopAEMC
.com
Shop for AEMC products online at:
1.888.610.7664