• Configure operating mode TAKT (see page 41, Operating mode and
load type).
• Turn potentiometer R201 TRAFO ADAPTION to left stop (see page
44, potentiometer).
• Connect signal generator (e.g. 2-point controller) to terminal X2.7.
> The device switches on at a signal level of > 3 V
5.7 Connecting the bus module
The way in which the bus module is connected to the power controller
decides the type of setpoint processing (see page 19, Setpoint pro-
cessing). Terminal X22.1 controls the processes (we recommend the
use of preassembled connection cable 2 000 000 848 / 849).
Setpoint of the anlogue control terminal only
• Do not make any connections to terminal X22.1.
>
Only the analog signal (X2.4 (+); X2.3 (ground)) is used as
setpoint.
Setpoint of bus module only
• Connect ground to terminal X22.1.
>
Only the value of the bus module is used as setpoint.
Defined setpoint for bus failure
There are two possibilities:
• Connect terminal X22.1 on the master of the power controller to
terminals X1.1 ... X8.1 of the bus module.
> Cable to X22.1 is switched in the event of a malfunction.
> In the event of malfunctions along the bus line, the system automa-
tically switches to the analog setpoint at the control terminals of the
power controller.
• Connect terminal X22.1 on the master of the power controller to
terminals X1.5 ... X8.5 of the bus module.
> Cable to X22.1 is switched in the event of a malfunction.
> Depending on the settings on the bus module:
In the event of malfunctions along the bus line, the system automa-
tically switches to the analog setpoint at the control terminals of the
power controller or the last setpoint is maintained. In addition to this,
each device connected to the bus module can be enabled individually
via the bus on „Hand“ (see bus module instructions).
Содержание THYRO-A
Страница 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Страница 39: ...39 EN l l Type plate 4 2 DIP switches S1 S1 10 S1 9 S1 8 S1 7 S1 6 S1 5 S1 4 S1 3 S1 2 S1 1 off on ...
Страница 70: ...70 Example 4 controllers e g with 100A load triggering approx 30 contents of Sync_Adr 0 100 25 50 75 ...
Страница 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Страница 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Страница 91: ...91 EN Thyro A 1A 280 HF M 10 for grounding Thyro A 1A 350A To unlock push spring hook to the right ...
Страница 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Страница 95: ...95 EN Thyro A 2A 280 HF M 10 for grounding Thyro A 2A 350A To unlock push spring hook to the right ...
Страница 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Страница 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Страница 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Страница 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Страница 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Страница 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Страница 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...