106
In Detail
Device application conditions
Built-in device (VDE0160)
EN 50 178
General requirements
EN 60146-1-1
Design, vertical installation
Operating conditions
EN 60 146-1-1; ch. 2.5
Area of application, industrial
CISPR 6
Temperature behaviour
EN 60 146-1-1; ch. 2.2
Storage temperature
D
-25°C - +55°C
Transport temperature
E
-25°C - +70°C
Operating temperature better B
-10°C - +35°C
with forced ventilation
-10°C - +45°C with natural air cooling
-10°C - +55°C
with reduced type current -2%/°C
Use of the device in UL conditions
up to a maximum ambient
temperature of 40°C.
Load category
1
EN 60 146-1-1 P.2
Humidity class
B
EN 50 178 Tab. 7 (EN 60 721)
Overvoltage category
III
EN 50 178 Tab. 3 (849V)
Degree of contamination
2
EN 50 178 Tab. 2
Air pressure
900 mbar*; 1000 m above sea level
Degree of protection
IP00
EN 69 529
Protection class
I
EN 50178 chap. 3
Air and creepage distances
housing / mains potential > 5.5 mm
housing / control pot. > 1 mm
mains volt. / control pot. > 10 mm
mains volt. among each other
2.5
mm
Mechanical shocks
EN 50 178 chap. 6.2.1
Test voltage
EN 50 178 tab. 18
Tests in acc. with
EN 60 146-1-1 4.
EMC emitted interference
EN 61000-6-4
Radio interference suppression
Control unit
Class A
EN 55011; CISPR 11
EMC interference immunity
EN 61000-6-2
Compatibility level
Class 3
EN 61000-2-4
ESD
8 kV (A) EN 61000-4-2
Electromagnetic fields
10 V/m
EN 61000-4-3
Содержание THYRO-A
Страница 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Страница 39: ...39 EN l l Type plate 4 2 DIP switches S1 S1 10 S1 9 S1 8 S1 7 S1 6 S1 5 S1 4 S1 3 S1 2 S1 1 off on ...
Страница 70: ...70 Example 4 controllers e g with 100A load triggering approx 30 contents of Sync_Adr 0 100 25 50 75 ...
Страница 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Страница 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Страница 91: ...91 EN Thyro A 1A 280 HF M 10 for grounding Thyro A 1A 350A To unlock push spring hook to the right ...
Страница 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Страница 95: ...95 EN Thyro A 2A 280 HF M 10 for grounding Thyro A 2A 350A To unlock push spring hook to the right ...
Страница 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Страница 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Страница 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Страница 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Страница 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Страница 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Страница 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...