Message
LED
LED
LED Internal Internal Internal
Description
ON PULSE LOAD LED at LED at LED at
INHIBIT FAULT Master Slave 1 Slave 2
(green)
(red)
(red)
(green)
(green)
(green)
Device without
OFF
OFF
OFF
OFF
-
-
Device not operating
voltage
supply
Voltage supply
ON
-
-
-
-
-
Voltage supply
present
present
Control
display
ON OFF
- Flash*
1
Flash*
1
Flash*
1
Depending on the control,
the interal LEDs flash at
diff. speeds, from completely
OFF to completely ON
Setting aid on
ON
Flash Flash
OFF
-
-
The analog output outputs a
analog output
fast
fast
potentiometer value 30 secs.
after the last potentiometer
change:
normal
mode,
alternating
flashing
Frequency error
ON
Flash
OFF
OFF
-
-
Frequency outside
slow
47Hz to 63 Hz
SYNC error
ON
Flash
OFF
OFF
-
-
Zero crossing of mains
slow
voltage
faulty
Device excess
ON
OFF
Flash
OFF
-
-
Excess temperature
temperature
slow
90°/95°C internal/external
Undercurrent in
ON
OFF
ON
OFF
-
-
Undercurrent limit
load
curcuit
exceeded
Flash
values
ON Flash*
1
Flash*
1
OFF
-
-
Parameters (in Flash)
invalid
fast
fast
faulty or deleted
Undervoltage
ON
ON
ON
ON
-
-
Mains voltage < than
in mains
undervoltage limit (-57%)
Pulse inhibition
ON
ON
OFF
OFF
-
-
Bridge X2.1 - X2.2 open
or set via bus
U limit
ON
Flash Flash
OFF
-
-
U, I, or P limit reached,
I limit
slow
slow
flash alternately
P
limit
No communication
ON
OFF
OFF
Flash
Flash
Flash
No communication with
with the
slow
fast
fast
the slave
slaves
Error rotating field / ON
Flash*
1
OFF Flash*
1
Flash
Flash
Left rotating field or
phase
slow slow fast fast
phase
missing
OFF LED not lights up
Flash slow
LED flashes slowly (1 Hz or 3.3Hz)
ON
LED permanentely lights up
Flash fast
LED flashes fast or flickers (14.7 Hz)
-
Any other state of the LED
*
1
LEDs flash simultaneously
When the semiconductor fuse is triggered, this causes a voltage
failure at the power controller. The device therefore switches off or
announces a frequency error.
LED messages
Содержание THYRO-A
Страница 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Страница 39: ...39 EN l l Type plate 4 2 DIP switches S1 S1 10 S1 9 S1 8 S1 7 S1 6 S1 5 S1 4 S1 3 S1 2 S1 1 off on ...
Страница 70: ...70 Example 4 controllers e g with 100A load triggering approx 30 contents of Sync_Adr 0 100 25 50 75 ...
Страница 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Страница 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Страница 91: ...91 EN Thyro A 1A 280 HF M 10 for grounding Thyro A 1A 350A To unlock push spring hook to the right ...
Страница 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Страница 95: ...95 EN Thyro A 2A 280 HF M 10 for grounding Thyro A 2A 350A To unlock push spring hook to the right ...
Страница 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Страница 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Страница 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Страница 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Страница 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Страница 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Страница 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...