5. Installation
DANGER
Dangers during Installation
Risk of injury / Risk of damage to the device or plant
> Observe all safety regulations in the safety chapter
DANGER
Unsafe system due to incorrect installation
The plant cannot be operated safely and poses a threat
to persons.
> Only install the device in an upright position.
> Ensure sufficient ventilation of the cabinet if mounted
in a cabinet.
> Observe minimum spacing (Clearance: 150 mm above,
100 mm below). The devices can be installed next to
each other without spacing between.
> Ensure that the device cannot be heated up by heat
sources below it. (The power loss is given in the type
overview table , see page 87, Technical data)
> Ground the device in accordance with local regulations.
(grounding screw / nut for protective conductor connec-
tion to fixing adapter). Grounding also serves for EMC
means (Y capacitor 4.7 nF).
CAUTION
Use of incorrect connection cables
Incorrect connection cables can lead to malfunctions.
Use shielded control conductors to connect the control
signals.
For use in UL conditions: Only use 60°C or 75°C
copper conductors for power connections (as indicated in
Technical Data).
Содержание THYRO-A
Страница 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Страница 39: ...39 EN l l Type plate 4 2 DIP switches S1 S1 10 S1 9 S1 8 S1 7 S1 6 S1 5 S1 4 S1 3 S1 2 S1 1 off on ...
Страница 70: ...70 Example 4 controllers e g with 100A load triggering approx 30 contents of Sync_Adr 0 100 25 50 75 ...
Страница 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Страница 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Страница 91: ...91 EN Thyro A 1A 280 HF M 10 for grounding Thyro A 1A 350A To unlock push spring hook to the right ...
Страница 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Страница 95: ...95 EN Thyro A 2A 280 HF M 10 for grounding Thyro A 2A 350A To unlock push spring hook to the right ...
Страница 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Страница 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Страница 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Страница 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Страница 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Страница 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Страница 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...