Setting aid for ...H RL1 and ...H RLP1
There is a setting aid for the potentiometers.
• Connect the measuring device to the analog output (X2.9 (+) to X2.5
ground).
> If a potentiometer is altered, the set value of the potentiometer is
output at the analog output and not the actual value.
> If the device is operated on mains voltage, the red LEDs flicker for
the duration.
> If the potentiometer is not greatly altered for 30 secs., the device
automatically switches back to output of the selected actual value.
Since the analog output is designed for 0 - 20mA / 10V, 10mA (or 5V)
correspond to 100%. This means that the set values can be read off
directly or in percentages of the nominal value.
Analog output setting aid
20,0 mA or10V
200%
10,0 mA or 5V
100% or 100°el.
5,0 mA or 2,5V
50% or 50°el
2,5 mA or 1,25V
25% etc.
Setting aid for ...H1, …H RL1 and ...H RLP1
There are two setting options:
• Count the no. of turns of the potentiometer. The potentiometers have
a setting range of 18 turns. (The setting range is not guaranteed and
may deviate. If accurate settings are required, the potentiometer
must be checked using a different method.)
• Visualize the setting with PC and THYRO-TOOL FAMILY.
4.3.1 Setting the transformer load (AN1, SST, T
0
)
The settings described are relevant in operating mode TAKT.
• Set transformer load and SST on potentiometer R201 TRAFO AD-
APTION (Default setting: 60° el. with Thyro-A 1A as well as 90° el.
with Thyro-A 2A and -A3A).
If wound core and toroidal core transformers are used, an optimiza-
tion of this setting can be required.
With Thyro-A 1A generally 80°el turn (to the right), with Thyro-A 2A
and Thyro-A 3A turn at smaller angles (to the left). An optimal setting
is achieved when the rush current is minimal.
Содержание THYRO-A
Страница 28: ...28 Possible settings in THYRO TOOL FAMILY ...
Страница 39: ...39 EN l l Type plate 4 2 DIP switches S1 S1 10 S1 9 S1 8 S1 7 S1 6 S1 5 S1 4 S1 3 S1 2 S1 1 off on ...
Страница 70: ...70 Example 4 controllers e g with 100A load triggering approx 30 contents of Sync_Adr 0 100 25 50 75 ...
Страница 89: ...89 EN 10 Type overview Thyro A 1A 16 H 30 H Thyro A 1A 45 H 60 H ...
Страница 90: ...90 75 190 Thyro A 1A 100 H Thyro A 1A 130 H 170 H M 10 for grounding ...
Страница 91: ...91 EN Thyro A 1A 280 HF M 10 for grounding Thyro A 1A 350A To unlock push spring hook to the right ...
Страница 92: ...92 Thyro A 1A 495A 650A Thyro A 1A 1000A 1500 A ...
Страница 95: ...95 EN Thyro A 2A 280 HF M 10 for grounding Thyro A 2A 350A To unlock push spring hook to the right ...
Страница 96: ...96 Thyro A 2A 495 650HF Thyro A 2A 1000 1500HF ...
Страница 97: ...97 EN Dimension drawing Thyro A 3A with 16A 30A The dimension drawings are for type H RLP1 ...
Страница 98: ...98 Dimension drawing Thyro A 3A with 45A 60A The dimension drawings are for type H RLP1 ...
Страница 99: ...99 EN Dimension drawing Thyro A 3A with 100A The dimension drawings are for type H RLP1 ...
Страница 100: ...100 Dimension drawing Thyro A 3A with 130A 170A The dimension drawings are for type H RLP1 ...
Страница 101: ...101 EN Dimension drawing Thyro A 3A with 280A The dimension drawings are for type H RLP1 ...
Страница 103: ...103 EN Thyro A 3A 1000 1500HF Thyro A 3A 495 650HF ...