Note
All event messages are cleared.
✔
Main menu
▶
System settings
▶
Clear event log
1.
Press
SET
2.
Press
SET
for 1 s to clear the event log.
Fig. 5:
Clear event log
dialog
Liste der Ereignismeldungen
DANGER!
When correcting errors, observe the safety instructions in
Event message
Cause
Remedy
No.
Text
26
System
voltage not
recognized
The automatically
detected system
voltage cannot be
matched to any of the
voltages 12 V/ 24 V/
48 V.
Take the following measures:
1. Switch off the DC load circuit breaker (solar
module) and secure it against being switched on
again. With 2 solar modules, switch off
both DC
load circuit breakers.
2. Determine the rated voltage of the system.
3. Check the following points:
‒
Is the manually set systems voltage the same as
the actual rated voltage of the system? Correct if
necessary!
‒
Does the battery voltage lie within the range of
the rated voltage of the system? If necessary,
charge the battery with an external charger.
29
Time not set
The time and date are
not set.
Set the time and date.
31
System
voltage
xx
V
detected
The controller has
detected a system
voltage of
xx V (battery
voltage).
The message is displayed after the battery has
been connected.
GB
749.126 | M02 | 2013-11-13