4.6
Installing the library
4.6.1
Choosing a location
Choose a location that meets the following criteria:
Table 4
Location criteria
Criteria
Definition
Rack requirements
Standard 19-inch rack with 2U of clearance
Room temperature
10-35º C (50-95º F)
Power source
AC power voltage: 100-127 VAC; 200-240 VAC
Line frequency: 50-60 Hz
Place the library near an AC outlet. The AC power cord is the pr
oduct’s main
AC disconnect device and must be easily accessible at all times.
Weight without
media
Single drive unit: 14.7 kg
Two drive unit: 15.6 kg
Weight with media
Single drive unit: 20.2 kg
Two drive unit: 21.1 kg
Air quality
The library should be placed in an area with minimal sources of particulate
contamination.
Avoid areas near frequently used doors and walkways, stacks of supplies that
collect dust, printers, and smoke-filled rooms.
Excessive dust and debris can damage tapes and tape drive.
Humidity
20-80 percent RH non-condensing
Clearance
Back: Minimum of 15.4 cm (6 inches)
Front: Minimum of 30.8 cm (12 inches)
– for mailslot
Minimum of xx cm to remove magazines
Sides: Minimum of 5.08 cm (2 inches)
Содержание actiLib Autoloader 2U
Страница 1: ...actiLib Autoloader 2U User and Service Guide Date September 17 2009 ...
Страница 10: ...Figure 63 Releasing the magazine 73 ...
Страница 21: ...Figure 9 Shipping lock before transportation 3 4 5 2 1 ...
Страница 31: ...5 7 OCP Menu Flow Charts Figure 17 OCP User interaction Mode actiLib Library 2U ...
Страница 32: ...Figure 18 Interaction Mode Information ...
Страница 33: ...Figure 19 Interaction Mode Information continuation ...
Страница 34: ...Figure 20 Interaction Mode Commands ...
Страница 35: ...Figure 21 Interaction Mode Configuration ...
Страница 36: ...Figure 22 Interaction Mode Configuration continuation ...
Страница 37: ...Figure 23 Interaction Mode Service ...
Страница 43: ...Figure 28 Slot numbering right magazine ...