Requirements For The Commonwealth Of Massachusetts

The following requirements reference various 

Massachusetts and national codes not contained in 

this manual. For all sidewall horizontally vented gas 

fueled equipment installed in every dwelling, building 

or structure used in whole or in part for residential 

purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent 

termination  is  less  than  (7)  feet  above  finished  grade 

in the area of the venting, including but not limited to 

decks and porches, the following requirements shall be 

satisfied:

INSTALLATION OF CARBON MONOXIDE 

DETECTORS

 At time of installation of side wall horizontally vented 

gas fueled equipment, the installing plumber or gas-

fitter shall observe that a hard wired carbon monoxide 

detector with an alarm and battery back-up is installed 

on  the  floor  level  where  the  gas  equipment  is  to  be 

installed. In addition, the installing plumber or gas-

fitter  shall  observe  that  a  battery  operated  or  hard 

wired carbon monoxide detector is installed on each 

additional level of the dwelling, building or structure 

served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property 

owner  to  secure  the  services  of  qualified  licensed 

professionals for the installation of hard wired carbon 

monoxide detectors. In the event that the side wall 

horizontally vented gas fueled equipment is installed 

in a crawl space or attic, the hard wired carbon 

monoxide detector with alarm and battery back-up 

may be installed on the next adjacent floor level. In the 

event that the requirements of this subdivision can not 

be met at the time of completion of installation, the 

owner shall have a period of thirty (30) days to comply 

with the above requirements; provided, however, that 

during said thirty (30) day period, a battery operated 

carbon monoxide detector with an alarm shall be 

installed.

APPROVED CARBON MONOXIDE DETECTORS

Each carbon monoxide detector as required in 

accordance with the above provisions shall comply 

with NFPA 720 and be ANSI/UL 2034 listed and IAS 

certified.

SIGNAGE

A  metal  or  plastic  identification  plate  shall  be 

permanently mounted to the exterior of the building at 

a minimum of eight (8) feet above grade directly in line 

with the exhaust vent terminal for the horizontally vented 

gas fueled heating the appliance or equipment. The 

sign shall read, in print no less the one-half inch (1/2”) in 

size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL 

OBSTRUCTIONS”.

INSPECTION

The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not 

approve the installation unless, upon inspection, the 

inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 

248 CMR 5.08 (2) (a) 1 through 4.

EXEMPTIONS

 The following equipment is exempt from 248 CMR 5.08 

(2) (a) 1 through 4: The equipment listed in Chapter 10 

entitled “Equipment Not Required To Be Vented” in the 

most current edition of NFPA 54 as adopted by the Board; 

and Product Approved side wall horizontally vented 

gas fueled equipment installed in a room or structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided: When 

the manufacturer of Product Approved side wall 

horizontally vented gas equipment provides a venting 

system design or venting system components with 

the equipment, the instructions provided by the 

manufacturer for installation of the equipment and the 

venting system shall include:

•  Detailed instructions for the installation of the venting 

system design or the venting system components; 

and

•  A complete parts list for the venting system design or 

venting system.

GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

When the manufacturer of Product Approved side wall 

horizontally vented gas equipment does not provide 

the  parts  for  venting  the  flue  gases,  but  identifies 

“special venting systems”, the following requirements 

shall be satisfied by the manufacturer:

•  The referenced “special venting systems” instructions 

shall be included with the appliance or equipment 

installation instructions and;

•  The “special venting systems” shall be Product 

Approved by the Board, and the instructions for 

that system shall include a parts list and detailed 

installation instructions.

A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions 

shall remain with the appliance or equipment at the 

completion of the installation.

Содержание AG26i

Страница 1: ...plus de renseignements veuillez consulter le site www P65warnings ca gov Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO I...

Страница 2: ...ratories Clackamas Oregon Standards ANSI Z21 88 2017 CSA 2 33 2017 Vented Gas Fireplace Heaters CSA 2 17 2017 Gas Fired Appliances for Use at High Altitudes CSA P 4 1 2015 Testing Method for Measuring...

Страница 3: ...5 8 372 L Back to Exhaust Center 5 3 8 137 M Height to top of unit 19 1 8 486 A D B Top View J H K L G Electrical Access Left Side View M C E Gas Line Access F Right Side View Part Assembly Overview...

Страница 4: ...h an ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Locate the manual valve installed by your qualified service technician 6 Turn the manual valve clockwi...

Страница 5: ...minimum of eight 8 feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating the appliance or equipment The sign shall read in print no less the...

Страница 6: ...front top or sides of it In high traffic areas In windy or drafty areas 6 This appliance reaches high temperatures Children and adults should be alerted to the hazards of high surface temperature and...

Страница 7: ...installed in accordance with local codes if any If none exist use the current installation code ANSI Z223 1 NFPA 54 in the USA CSA B149 1 in Canada is mobile home approved must be properly connected t...

Страница 8: ...mon vent systems WARNING Do not pack the open air spaces with insulation or other materials This could cause high temperatures and may present a fire hazard and serious injury property damage or loss...

Страница 9: ...the co linear flexible aluminum pipe required for your installation inches mm A Height 20 508 B Front Width 31 788 C Depth 17 432 D Back Width 19 483 C A B D WARNING Any chimney clean outs must fit pr...

Страница 10: ...cm B Clearance to window or door that may be opened 6 15 cm for appliances 10 000 Btu h 3 kW 12 30 cm for appliances 10 000 Btu hr 3 kW and 100 000 Btu h 30 kW 36 91 cm for appliances 100 000 Btu h 3...

Страница 11: ...t fan operation If the gas fireplace insert is to be installed into minimum opening dimensions the gas line may need to be run after appliance placement due to space limitations ELECTRICAL WIRING Prov...

Страница 12: ...s noncombustible per ASTM E 136 1 OPTIONAL Before installing vent system down through the chimney place unfaced insulation around the first 3 ft 914 mm of vent system below termination cap Secure with...

Страница 13: ...e are aligned with the air duct 2 Insert the air duct pull rod handle through access slot at the top of appliance and place pull handle hook through the hole in pull rod Simultaneously push the gas in...

Страница 14: ...d from the gas supply piping system during any pressure testing of that system at pressures in excess of 1 2 psi 3 5 kPa For test pressures equal to or less than 1 2 psi 3 5 kPa the appliance must be...

Страница 15: ...nly authorized parts and materials when replacing defective or damaged glass WARNING Do not operate this fireplace with the glass removed cracked or broken Replacement of the glass assembly should be...

Страница 16: ...batteries to operate Using the battery back up will operate the burner only Light and blower components will not function on battery back up power CAUTION Check all connections for leaks with soapy wa...

Страница 17: ...17 Wiring Schematics MALE END VARIABLE SPEED FAN VARIABLE LIGHT APPLIANCE GROUND STAR BATTERY PACK 885 PROFLAME MAIN ON OFF SWITCH PILOT PILOT BURNER FLAME SENSOR IGNITER SW1 BUTTON RED...

Страница 18: ...e is located in the bottom cavity of the firebox Complete Valve Assembly To make working on components easier this fireplace has been designed with the valve pilot shutter boxes shutter cables and gas...

Страница 19: ...r Cable Shutter Cable Tube MTG Brkt Shutter Adjustment Sleeve Shutter Adj Top Assembly Shutter Adj Bottom Assembly Bulk Head Burner Orifice Pilot MTG Box Weldment Burner Mount Plate Valve Assembly Mou...

Страница 20: ...burner cycles on off without delays F Flame is stable and does not lift off burner If flame lifts off burner turn off and check that all vent pipes are twist locked and leak proof the vent cap is righ...

Страница 21: ...to provide continual efficient heat All other functions of the normal thermostat mode except the flame height adjustment are allowed Manual flame height adjustment is not allowed in this mode The Sma...

Страница 22: ...t IPI AND CPI MODES Intermittent Pilot and Continuous Standing Pilot Features First lights a pilot then uses the pilot to ignite the main burners The pilot can be set in the CPI Continuous Pilot Ignit...

Страница 23: ...ter will begin to spark After the pilot lights and is established the valve will automatically open and the burner will light The burner will initially light to full flame Adjust it to an appealing se...

Страница 24: ...r fabriqu e tats Unis seulement ou une maison mobile install e en permanence l o les codes locaux le permettent Voir le manuel d installation du foyer pour les d tails Cet appareil ne doit pas fonctio...

Страница 25: ...the pilot and under side of the logs for any carbon deposits Logs should be visually checked for carbon buildup If carbon deposits are visible on logs turned off and contact an authorized service pers...

Страница 26: ...m operating a child lock function is provided with this remote control system To activate the child lock function Simultaneously press the MODE button and the UP button To deactivate the child lock fu...

Страница 27: ...TURN ON If your remote control is working but your fireplace won t turn on it may be in lockout mode To reset a lockout follow these steps 1 Turn off remote 2 Turn on remote and wait 2 seconds 3 Turn...

Страница 28: ...ax Inlet Pressure Tap A 5 10 5 WC 1 25 2 62 kPa 12 14 WC 2 99 3 48 kPa Manifold Pressure Fuel Natural Gas LP Gas Gas Supply Low High Low High Manifold Pressure Tap B 1 1 3 8 WC 0 27 0 95 kPa 2 9 11 WC...

Страница 29: ...lator Issue Cause Solution Pilot will not light Electrical power interrupted or disconnected Restore electrical power to fireplace or use battery back up Wiring disconnection Ensure batteries are full...

Страница 30: ...ir if necessary Excessive draft A restrictor may need to be installed or modified Soot appears on glass Improper log placement Refer to Log Set Installation section Improper venturi setting Venturi ai...

Страница 31: ...and other flammable vapors and liquids CAUTION Label all wires prior to disconnection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after se...

Страница 32: ...32 Notes...

Страница 33: ...33 Notes...

Страница 34: ...ts bris s ou endommag s de l assemblage vitr AVERTISSEMENT Tout panneau barri re ou cran qui a t retir pour un entretien doit tre r install avant r utilisation Effectu par Propri taire Fr quence Annue...

Страница 35: ...Assemblage du cadre vitr Installation du chapeau d vent incorrecte Ajustez si n cessaire Blocage du chapeau d vent Si n cessaire retirez les d bris Mauvais niveau de l vacuation horizontale Une l vati...

Страница 36: ...r ou un fournisseur de gaz Cela peut tre caus par des situations comme une conduite courb e un diam tre ou un tuyau trop troit ou une faible pression Une flamme de la veilleuse n est pas en contact av...

Страница 37: ...po pour le gaz naturel ou 1 8 po 1 4 po pour le gaz PL Assurez vous que le br leur et les b ches sont correctement install s Apr s que le br leur a t correctement install et qu il a bien fonctionn pe...

Страница 38: ...la t l commande S lectionnez le mode CPI pour relancer la veilleuse Apr s la mise en route de la veilleuse mettez votre t l commande en marche pour allumer Apr s avoir suivi ces tapes contactez votre...

Страница 39: ...des de la t l commande avant que les piles n aient plus du tout d nergie Cette ic ne dispara t lorsqu on a remplac les piles POURQUOI MON THERMOSTAT DISPARA T IL DE MA T L COMMANDE Lors du changement...

Страница 40: ...et les d p ts de carbone sous les b ches Les b ches doivent tre v rifi es visuellement pour d tecter l accumulation ventuelle de carbone Si des d p ts de carbone sont visibles sur les b ches teignez...

Страница 41: ...reinstall per instructions with initial installation SAFETY BARRIERS For use only with barriers part numbers 611010 Follow installation instructions accompanying the appliance REPLACEMENT FAN KIT Par...

Страница 42: ...mage et la stabilisation de la veilleuse la vanne va s ouvrir automatiquement et le br leur va s allumer Le br leur va s allumer initialement pleine flamme Adaptez la un environnement attrayant avec l...

Страница 43: ...llement MODES IPI ET CPI Les fonctions de veilleuse intermittente IPI et veilleuse continue constante CPI allument d abord une veilleuse puis l utilsent pour allumer les br leurs principaux On peut r...

Страница 44: ...ajuste automatiquement pour fournir une chaleur constante et efficace Toutes les autres fonctions du mode normal sont permises sauf le r glage de la hauteur de flamme Le r glage manuel de la hauteur d...

Страница 45: ...ppareil tant que le br leur passe sans d lai de la position marche arr t F La flamme est stable et ne se d colle pas du br leur Si la flamme se d colle du br leur mettez hors tension et v rifiez que t...

Страница 46: ...rateur Manchon d ajustement de l obturateur R glage de l obturateur Assemblage sup rieur R glage de l obturateur Assemblage inf rieur T te du br leur Orifice du br leur Bo tier soud de la veilleuse Pl...

Страница 47: ...composants ce foyer a t con u avec la vanne la veilleuse les caissons obturateurs les c bles obturateurs et les conduites de gaz en tant que pi ces d un assemblage pouvant tre retir es Module de comma...

Страница 48: ...V type AA 1 5 V type AA 1 5 V type AA 1 5 V type AA 885 PROFLAME INTERRUPTEUR PRINCIPAL MARCHE ARR T FUSIBLE 3 15 A T VEILLEUSE BR LEUR D TECTEUR DE FLAMME ALLUMEUR BOUTON SW1 ROUGE MARCHE ARR T MOTEU...

Страница 49: ...ou contr le de gaz ayant t immerg e dans l eau AVERTISSEMENT Instructions de mise la terre Cet appareil est quip d une fiche trois broches de mise la terre pour votre protection contre les risques d...

Страница 50: ...languettes se trouvant en haut de la bo te combustion INSTALLER L ASSEMBLAGE VITR 1 Alignez les encoches en haut de la vitre par dessus les languettes se trouvant en haut de la bo te combustion tout...

Страница 51: ...mat riaux homologu s lors du remplacement d une d fectueuse ou endommag e AVERTISSEMENT Tenir compte de la hauteur du mat riau de finition de l tre lors de la construction d une plateforme L installat...

Страница 52: ...qualifi e conform ment aux codes du b timent locaux le cas ch ant Dans le cas contraire suivez la norme ANSI 223 1 Les installations du Commonwealth of Massachusetts doivent tre effectu es par un plom...

Страница 53: ...ur fixer le chapeau de sortie de la chemin e la chemin e appliquez une quantit g n reuse de cordon de p te sceller pour les temp ratures lev es autour de la partie sup rieure de la chemin e Fixez le c...

Страница 54: ...ez le couvercle de la chemin e existante CONDUITE DE GAZ Une conduite de gaz doit pouvoir tre install e l encastrable voir la rubrique intitul e Raccordement de la conduite de gaz du pr sent manuel Si...

Страница 55: ...gagement c t d une ou d une porte pouvant tre ouverte 6 po 15 cm pour les appareils 10 000 Btu h 3 kW 12 po 30 cm pour les appareils 10 000 Btu hr 3 kW et 100 000 Btu h 30 kW 36 po 91 cm pour les app...

Страница 56: ...t appareil ne doit ni partager ni tre connect un conduit de fum e desservant un autre appareil Emplacement De Sortie Les chapeaux d vent approuv s exige un d gagement de 305 mm 12 po autour des parois...

Страница 57: ...min e en ma onnerie Diam tre int rieur minimal de 152 mm x 203 mm 6 po x 8 po pouces mm A Hauteur 20 508 B Largeur avant 31 788 C Profondeur 17 432 D Largeur arri re 19 483 Exigences Du Foyer Existant...

Страница 58: ...clut entre autres le contreplaqu les cloisons s ches ou les panneaux de particules Les mat riaux combustibles peuvent tre en contact avec les c t s le bas ou l arri re de la bo te combustion Ne pas su...

Страница 59: ...pi ce o l appareil est install Les enfants en bas ge et autres sont susceptibles de se br ler par contact acciden tel Nous recommandons l existence d une barri re physique s il y a les personnes risqu...

Страница 60: ...acu horizontalement de l appareil ou l quipement de chauffage La plaque doit comporter l inscription suivante en caract res d au moins un demi pouce 1 2 po VACUATION DE GAZ JUSTE EN DESSOUS NE PAS OBS...

Страница 61: ...odeur de gaz ARR TEZ Passez l tape B des instructions de s curit sur la portion sup rieure de cette ttiqutte S il n y a pas d odeur de gaz passez l tape suivante 8 Tournez le robinet en sens antihorai...

Страница 62: ...3 8 137 M Hauteur au dessus de l unit 19 1 8 486 A D B vue de dessus J H K L G lectrique Acc s vue de gauche M C E F Ligne de gaz Acc s vue du c t droit Aper u De L assemblage Des Pi ces AVERTISSEMENT...

Страница 63: ...17 Appareils au gaz destin s la haute altitude CSA P 4 1 2015 M thodes de test pour mesurer l efficacit annuelle du foyer Cette installation doit tre conforme aux codes locaux ou en l absence de ceux...

Страница 64: ...t de cet appareil ou un autre QUE FAIRE SI VOUS D CELEZ UNE ODEUR DE GAZ N allumez aucun appareil N appuyez sur aucun interrupteur lectrique et n utilisez aucun t l phone dans le b timent Quittez imm...

Отзывы: