
-14-
Gas Line Connection
GAS CONVERSION (SOLD SEPARATELY)
This fireplace is manufactured for use with natural gas. Follow the instructions included with the AG26LPC
conversion kit if converting to LP gas.
GAS LINE INSTALLATION
Inlet Gas Supply Pressures
Fuel
Minimum Pressure
Maximum Pressure
Natural Gas
5” WC (1.25 kPa)
10.5” WC (2.62 kPa)
LP Gas
12” WC (2.99 kPa)
14” WC (3.48 kPa)
Facing And Finishing
12”
(305mm)
30”
(762mm)
10”
(254mm)
COMBUSTIBLE
MANTEL
COMBUSTIBLE
MATERIAL
9” (229mm) CLEARANCE
TO ADJACENT SIDEWALL
Mantel Requirements
CLEARANCES TO COMBUSTIBLES
CAUTION: Installation of the gas line must only be done by a qualified person in accordance with local building
codes, if any. If not, follow ANSI 223.1. Commonwealth of Massachusetts installations must be done by a
licensed plumber or gas fitter.
CAUTION: The conversion shall be carried out in accordance with the requirements of the provincial authorities
having jurisdiction and in accordance with the requirements of the ANSI Z223.1 installation code.
NOTE: The appliance and its individual shutoff valve must be disconnected from the gas supply piping system
during any pressure testing of that system at pressures in excess of 1/2 psi (3.5 kPa). For test pressures equal to
or less than 1/2 psi (3.5 kPa), the appliance must be isolated from the gas supply piping system by closing its
individual manual shut-off valve. A listed (and Commonwealth of Massachusetts approved) 1/2” (13 mm) tee
handle manual shut-off valve and flexible gas connector are to be connected to the 1/2” (13 mm) control valve
inlet. If substituting for these components, please consult local codes for compliance.
• If installing this insert into minimum opening dimensions, the gas line may need to be run after placement due
to space limitations (see the Existing Fireplace Opening Minimum Requirements section of this manual).
•
This fireplace is equipped with a 3/8” (10 mm) x 18” (457 mm) long flexible gas connector and manual shut-off
valve.
•
Run gas line into fireplace, preferably through left or right gas line holes provided. The gas line should be run to
the point of connection where the shut-off valve and flexible gas line will connect.
• Do not run gas line in a manner that would obstruct fan operation.
• For high altitude installations, consult the local gas distributor or the authority having jurisdiction for proper
rating methods.
Содержание AG26i
Страница 32: ...32 Notes...
Страница 33: ...33 Notes...